TBB Transformer 1+1 Inverter TN5000 for heavy industry, railway and transmisstion substation0 pages
TBB POWER CO.,LTD.
Tel: 86-592-5212299 Fax: 86-592-5796070
website: www.tbbpower.com
Email: sales@tbbpower.com
TN5000 Isolated UPS
Electrical
Safety & Enviroment
TN5101 - TN5120
TN5304 - TN5360
Model
AC Input
TN5100
TN5300
Voltage
Frequency
Voltage
Frequency
Bypass
DC Input
Norminal Voltage
Operating range
AC Output
TN5100
Power
TN5300
Wave form
Power factor
Rated Ouput Voltage
Voltage variation
Output frequency
220VAC: -25% -- +20%
50Hz ±10%
380VAC: -20% -- +20%
50Hz ±10%
220VAC: -25%-+20%
220VDC / 110VDC
183-272VDC / 91.5-136VDC
1KVA - 20KVA
4KVA - 60KVA
Pure Sine Wave
0.8
110/120VAC, 220/230/240VAC
Max ± 2%
50/60Hz ± 0.1%
<1% liner load
THD
<5% non-liner load
Crest Factor
.3:1
Efficiency
Max 85%
150% 1min
Overload
125% 10min
0ms
Transfer Time
4ms (to bypass)
Dynamic transfer time < 20ms
Operating Temp.: -10C - 50C
Storage Temp. : -40C - 85C
Isolation
AC - DC
: 2000Vrms
DC - ground : 2000Vrms
AC - ground : 2000Vrms
Display & Communication
LCD + LED
All parameters
Working mode
Fault
Communication RS485 and RS232
Interface
6xDry contact
Mechanical
Cooling
Protection
forced fan
IP20
Standard
Safety
Emmission
Immunity
EN60950-1
EN55022
EN55022