Close Loop DC Current Sensor SCB19 Series - Socan0 pages
Socan SCB19 technical parameters
Model
Parameters(25°C)
Nominal Rms Current (Ipn)
Input pin size
Measuring Range (Ip)
Load resistance Rmax
Turns Ratio
Output Voltage
Working voltage
Accuracy @ Ta=25°C
Linearity @ Ta=25°C
Withstand voltage
Zero Output
Offset temperature
Themal drift of Vo
Hysteresis offset
Reponse time
Current consumption
Operating temperature
Storage temperature
g
p
Dimension(mm)
SCB19D5A
10A
15A
20A
25A
30A
50A
±5A
±10A
±15A
±20A
±25A
±30A
±50A
ø8.0
2*Ipn
≥10kΩ
1:500
1:625
1:1000
2.5±2.0V
DC + 5V (±5%)
±1% FS
±1% FS
2.5kVrms/50Hz/min
2.5V < ±1%
< ±0.08%/°C
< ±0.05%/°C
< ±0.2%/°C
< ±0.1%/°C
< ±60mV (if=F.S. 0<--- --->Norminal RMS Current)
< 3uS
<20mA
-40~+80 °C
-40~+85 °C
Size Description: In addition to
calibrated, the remain
deviation: ±0.3
Instructions
1. Single power supply, working voltage: +5 V (± 1% )
2. Voltage output.
3. Zero output is 50% of the supply voltage.
4. Fluctuations in the supply voltage will affect the zero output, it is recommended to add a supply
voltage regulator device, such as a zener diode, etc.
5. Users of sampling resistor must be greater than 10KΩ
6. We can customize different current and voltage output according to the user's requirements.
Caution: Incorrect wiring may cause damage to the sensor