YT-27010 pages
YOUNG TECH FRANCE
■www.ytc-frarice.fr
I Smart Positioner YT-2701
Product Number: YT-2701 □□□□□□□□□
Model Motion Acting Explosion Proof Lever Type Connection Communication Option Fail Option Cable
YT-2701 ■ Linear [s] Single [n] Non-Explosion \T\ 5^50 mm [T] PT [0] None [0] None [F] Fail Freeze 05m
[c]Exia IICT5/T6 \Y\ NPT [2] HART [T] PTM [s] Fail Safe 010m
0 15m
020m
YT-2701
CABLE CONNECTOR
\57 | 51.4 I 3.5
\ 4-M6'1.0PTAP
Body
Sensor
Item - Type | YT-2701 | |
Input Signal | 4-20mA VDC | |
Supply Pressure | 0,14-0,7MPa (1,4-7 bar) | |
Stroke | 5^50 mm | |
Impedance | Max 500Q @ 20mA | |
Connection | Air | (N)PT1/4" |
Gauge | (N)PT1/8" | |
Conduit | PF(G)1/2" | |
Temperature | Standard | -30^80°C |
Linearity | ±0,5% F.S. | |
Hysteresis | ±0,5% F.S. | |
Sensitivity | ±0,2% F.S. | |
Repeatability | ±0,3% F.S. | |
Consumption - Air | 0,01 lpm@0,14MPa | |
Flow Capacity | 9 Ipm @ 0,14MPa | |
Output Characteristics | Linear, EQ%, Quick Open, User Set (16 points) | |
Material | Aluminium | |
Enclosure | IP 66 | |
Explosion Proof | Exia IICT5/T6 | |
Weight | 0,82 kg |
YT-2701 accurately controls valve stroke, according to input signal 4-20mA being delivered from
controller.
• Fail function • Near zero air consumption level • HART Communication
• Auto-calibration • PD Control • 4 buttons for local control
• LCD Display • Feedback signal (PTM) • Single acting only
More Information : www.ytc-france.fr/EN-2701.html
"