YT-25010 pages
YOUNG TECH FRANCE
^^^^^^^^^^^^■www.ytc-france.fr
Smart Positioner YT-2501
Product Number: YT-2501 □□□□□□□□□
LGVGT
Model Motion Acting Explosion Proof Ljnear Rotary Connection Comm. Option Fail Option Cable
YT-2501 [J_] Linear [s] Single ■ Non-Explosion [T] 10^40 mm [J] NAMUR [T] PT [5] None [5] None [f] Fail Freeze [l]5m
[R] Rotary [D] Double [c] Ex ia IIC T5/T6 [2] 20^70 mm ■ NPT [2] HART [T] PTM* [s] Fail Safe [2] 10m
[3] 50^100 mm [3] F. Fieldbus* [3] 15m
[4] 100^150 mm [4] 20m
Incompatible : Ex ia IIC T5/T6
incompatible: F. Fieldbus
YT-2501 R
(Sensor)
YT-2501 L
YT-2501 R (Body)
CABLE CONNECTOR
CABLE CONNECTOR 91.5
13.5 35 24.3
4-M5*0.8PTAP DP. 11
m^gi 4-M6M.0PTAP
Item - Type | YT-2501 L | YT-2501 R | |
Input Signal | 4-20mA VDC | ||
Supply Pressure | 0,14-0,7MPa (1,4-7 bar) | ||
Stroke | 10^150 mm | 0^90° | |
Impedance | Max 500Q @ 20mA | ||
Connection | Air | (N)PT1/4" | |
Gauge | (N)PT1/8" | ||
Conduit | PF(G)1/2" | ||
Temperature | Body | -40^120°C | |
Sensor | -30^80°C | ||
Explosion | -40^60°C (T5) -40^40°C (T6) | ||
Linearity | ±0,5% FS. | ||
Hysteresis | ±0,5% FS. | ||
Sensitivity | ±0,2% FS. | ||
Repeatability | ±0,3% FS. | ||
Consumption -Air | F. Freeze | 0,01 L/min@0,14MPa | |
F. Safe | 6 L/min @ 0,14MPa | ||
Flow Capacity | 60 L/min @ 0,14MPa | ||
Output Characteristics | Linear, EQ%, Quick Open, User Set (16 points) | ||
Material | Aluminium | S.S. 316 | |
Enclosure | IP 66 | ||
Explosion Proof | Ex ia IICT5/T6 | ||
Weight | Body | 1,5 kg | |
Sensor | 0,6 kg | 0,9 kg |
YT-2501 L (Sensor)
YT-2501 R (Body)
YT-2501 supplies remote functions and higher liabilities in high temperature and vibration
environment.
• Separated feedback module • Near zero air consumption level • HART Communication
• Auto-calibration • PD Control • 4 buttons for local control
• LCD Display • Feedback signal (PTM) • Fail function
More Information : www.ytc-france.fr/EN-2501.html
"