Fuel Monitors 0 pages
copyright 2006
www.facetinternational.com
HFG Series Horizontal
Fuel-Gard® Monitor Housings
ELIMINATE THE NEED FOR OTHER WATER
DEFENSE DEVICES AND RECEIVE MAXIMUM
WATER REMOVAL, SOLIDS HOLDING CAPACITY
AND SHUTDOWN PROTECTION TO ASSURE
CLEAN, DRY FUEL DELIVERY WHILE MEETING
THE LATEST EDITION OF E.I. SPECIFICATION
#1583.
The new Facet HFG Series Horizontal Fuel-Gard
monitor housings, equipped with either Facet’s FG
Series or PS Series 2" (51 mm.) OD monitor
cartridges, continually check the entire flow of
fuel, not just mere samples, for water or solids
contamination. By performing three jobs, the FG
Series monitors assure clean, dry fuel. They absorb
free and emulsified water, remove ultra-fine solids,
and shut down system flow when hit with a localized
slug of water. In addition, the PS Series monitors
positively shut down system flow when pressure
drop across the cartridge exceeds 40 psi eliminating
any possibility of media or water transmission while
also preventing the system being reused. They are
designed to flow from the outside to inside at a rate of 1
gallon (3.79 liters) per inch of length.
Facet’s Fuel-Gard monitor housings are built to ASME
Code, constructed of carbon steel and designated
for maximum working pressure of 150 psi. They are
furnished with FG Series monitor cartridges that meet
and exceed the latest edition of E.I. specification
#1583 Aviation Fuel Filter Monitors With Absorbent
Type Elements.
Facet’s GNG Series monitor cartridges are interchangeable
with the FG Series when
MIL-M-81380C(AS) requirements are desired.
STANDARD HOUSING DESIGN
• Welded carbon steel construction—other materials
available on request
• ASME Code, Section VIII construction, stamped
and certified
• Maximum working pressure: 150 psi
• Swing bolt closures on 85..8" (219 mm.) OD housings
and larger
• Buna-N closure o-ring—other materials available
• Exterior: Prime coated
• Interior: Epoxy coated
• Spider plate
STANDARD CONNECTIONS
• Flanged inlet and outlet connections
• Drain connection: 3..4" NPT
• Vent and relief valve connections: 3..4" NPT
• Differential pressure gauge connections: 1..4" NPT
OPTIONS
• Automatic air eliminator
• Pressure relief valve
• Differential pressure gauge
• Sampling probes
• Manual drain valve
• Victaulic inlet and outlet connections
• Interlock Device
A-501