MAXFire 100 Series Igniter Technical Bulletin0 pages
MAXFire® Series 100 Gas Igniters
A UTC Fire & Security Company
MAXFire® gas igniters provide the most
reliable source of energy for main flame
ignition, flame stabilization, and boiler
warm-up.
Features & Benefits
Product Overview
• Class 1, 2 or 3 Gas Igniter t
C
apacity range from 0.3 to 50 MBtu/hr.
• Application Flexibility t
The protected primary combustion zone
ensures reliable operation in multiple
environments.
installed as a retrofit into most burner types based on its size, capacity, and reliable
• Reliable Ignition t
9
9% ignition rate in most applications.
• Cooling / C ombustion Airt
Low cooling/combustion air requirements.
• Low Maintenance Requirementst
No
moving parts, a self-cleaning spark tip
and no tools required to perform periodic
inspection.
The MAXFire® Series 100 gas igniters can be used as a Class 1 , Class 2, or
Class 3 igniter, depending on burner capacity. The MAXFire® igniter is easily
operation.
MAXFire® gas igniters consist of four major components: a guide tube, a
gas transport tube, a spark rod, and a stainless steel diffuser for pilot stabilization.
The guide tube houses the spark rod and the gas transport tube, which are easily
removed from the guide tube for maintenance purposes by releasing a "V" band
retainer, requiring no tools. Cooling/combustion airflow is directed down the guide
tube to support and maintain the primary combustion zone during operation. The
controlled mixture of fuel and air in the primary combustion zone results in a
highly reliable, stable igniter flame. While out of service, airflow cools the igniter
• Durability
Heavy duty material and no moving parts
to wear out.
and prevents debris from migrating into the end of the guide tube.
• Compatibility
Fits most existing mount tubes minimizing
retrofit installation costs.
Igniter (HESI) as the spark source. The HESI produces a powerful 12-joule
• Spark Source Options t
The nonfouling HESI comes standard.
HTSI provides high performance at an
economical price.
a threaded connection. Optional equipment for the MAXFire® includes a High
MAXFire® gas igniters come standard with Forney’s High Energy Spark
spark approximately three times per second at the primary combustion zone. The
HESI spark tip is a nonfouling, surface-gap tip which is replaceable as a unit by
Tension Spark (HTSI) source in place of the HESI, mounting hardware, hoses,
flame rod and an integral or externally mounted optical flame detector.
Forney Corporation • 3405 Wiley Post Road • Carrollton, TX 75006 • 800-356-7740 • Fax 972-458-6650 • www.forneycorp.com