ICG 653/UNIV/L0 pages
Flameproof, Increased Safety, Dust Protection
n
Class - Zones - Divisions
Certified ATEX / IECEx / c CSA us
'T'
'G'
'F'
'E'
'D'
Application
ø 'B'
(for Lead Sheath Cables)
Outdoor or indoor use.
For use with single wire armour ‘W’, wire braid ‘X’, steel
tape armour ‘Z’, elastomer and plastic insulated cables
with a lead inner sheath.
For particular use with:- Cables that are not effectively filled, compact and/or
circular, have tape bedding or have hygroscopic fillers.
- Cables that exhibit ‘Cold Flow’ characteristics.
- Enclosures containing an ignition source in gas group
IIC areas or containing an ignition source in a Zone 1
area.
See technical section for installation rules and regulations.
ICG 653/UNIV/L
Group II Cable Glands
CABLE GLAND SELECTION TABLE
Entry Thread Size 'F'
Size
Ref.
Cable Acceptance Details
Inner Sheath / Cores
Metric
NPT *
Standard or
Option
' D ' Max.
Over Cores
Os
M20
½"
8.5
10.0
12
O
M20
½"
8.5
10.0
12
A
M20
¾" or ½"
10.8
12.5
Outer Sheath 'B'
NOTE 1 NOTE 2
Max Inner
Max. No. Max. No.
Sheath ‘E’
of Cores of Cores
Hexagon
Dimensions
Armour / Braid 'C'
'G'
Across Across
Flats Corners
Min.
Max.
Orientation 1 Orientation 2
6
5.5
12.0
0.8 / 1.25
0.0 / 0.8
67.0
24.0
26.5
6
9.5
16.0
0.8 / 1.25
0.0 / 0.8
67.0
24.0
26.5
15
10
12.5
20.5
0.8 / 1.25
0.0 / 0.8
67.0
30.0
32.5
B
M25
1" or ¾"
16.2
18.4
30
21
16.9
26.0
1.25 / 1.6
0.0 / 0.7
73.6
36.0
39.5
C
M32
1¼" or 1"
21.9
24.7
42
42
22.0
33.0
1.6 / 2.0
0.0 / 0.7
78.0
46.0
50.5
C2
M40
1½" or 1¼"
26.3
29.7
60
60
28.0
41.0
1.6 / 2.0
0.0 / 0.7
82.4
55.0
60.6
D
M50
2" or 1½"
37.1
41.7
80
80
36.0
52.6
1.8 / 2.5
0.0 / 1.0
88.7
65.0
70.8
E
M63
2½" or 2"
47.8
53.3
100
100
46.0
65.3
1.8 / 2.5
0.0 / 1.0
92.7
80.0
88.0
F
M75
3" or 2½"
59.0
64.0
120
120
57.0
78.0
1.8 / 2.5
0.0 / 1.0
99.4
95.0
104.0
'T' — All dimensions in millimetres (except * where dimensions are in inches). Metric entry threads are 1.5mm pitch as standard, 15mm length of thread.
Note 1: ATEX / IECEx certification only - Note 2: All other certification.
Technical Data
Ordering Information
Flameproof Exd IIC Gb, Increased Safety Exe IIC Gb and Dust Extb
IIIC Db II 2 GD.
Certificate No’s: Baseefa06ATEX0058X and IECEx BAS 06.0015X.
Suitable for use in Zone 1, Zone 2, Zone 21, Zone 22 and in Gas
Groups IIA, IIB and IIC.
Construction and Test Standards: IEC/EN 60079-0, IEC/EN 60079-1,
IEC/EN 60079-7 and IEC/EN 60079-31.
Ingress Protection: IP66, IP67 and IP 68 (30 metres for 7 days) to
IEC/EN 60529 and NEMA 4X.
Deluge Protection to DTS01.
Operating Temperature Range: -60°C to +80°C.
Assembly Instruction Sheet: AI 301 and AI 336.
Format for ordering is as follows: Alternative Seal (AR), add suffix
AR to ordering information.
Cable Gland Type
Size
Thread
Lead
Material
(Optional)
ICG 653/UNIV
ICG 653/UNIV
C
C
M32
1 ¼" NPT
L
L
Brass
Brass
AR
AR
Features
Provides an inspectable, repairable barrier seal to the individual insulated cores
within the cable, and prevents entry of the products of an explosion into the cable.
Assembly of the cable gland compresses and distributes the compound evenly to
create a barrier seal at the point of entry into the enclosure.
Provides armour clamping, using one clamping arrangement for all armour / braid
types.
Provides a seal and an electrical bond on the cables lead inner sheath.
Provides an outer deluge seal to prevent moisture ingress to the cable armour /
braid.
Provides a cable retention and low smoke and fume, zero halogen seal onto the
cables outer sheath.
Manufactured in Brass (standard), Nickel Plated Brass, 316 Stainless Steel or Aluminium.
Brass NPT entries are nickel plated as standard.
Alternative Reversible Armour Clamping Rings (RAC)
SELECTION TABLE
Size Ref.
B
C
C2
D
E
F
Steel Wire Armour / Braid / Tape
Orientation 1
Orientation 2
0.9 - 1.25
0.5 - 0.9
1.2 - 1.6
0.6 - 1.2
1.2 - 1.6
0.6 - 1.2
1.45 - 1.8
1.0 - 1.45
1.45 - 1.8
1.0 - 1.45
1.45 - 1.8
1.0 - 1.45
Connection Solutions
UPD 141114
www.ehawke.com
Alternative certification options available:
Two part sealing compound and assembly instructions are supplied
with the cable gland.
93
"