Distribution Automation_INGESAS_PM0 pages
ingepac
DA
Control unit
for distribution applications
INGEPACTM DA covers a wide range of applications making it possible to use one single device to fulfil
every automation, protection, measurement and telecontrol requirement, both for RMUs and LBSs.
INGEPACTM DA is characterised by a modular structure which makes it possible to incorporate plug-in
signal capturing modules, depending on your specific requirements and the number of elements to be
monitored.
Automation control unit
CENTRE 2L+P
Applications
∙∙ Ring Main Units control and compact
transformer substations.
∙∙ Overhead distribution application
control (LBS, etc.).
∙∙ Mini RTU for small power plants.
52 (89)
Automation
52 (89)
Signalling
74TC
74CC
4
4
Fault
detection
50/51
50/51N
>V
BASIC FUNTIONS
∙∙ Automation, Supervision and Protection
Functions
∙∙ Realtime monitoring of the
installation’s signals
∙∙ Local and remote operation of all
transformation elements.
∙∙ Voltage detection
∙∙ Directional fault detection.
∙∙ Slack springs
∙∙ Fault isolation automatic operation.
∙∙ 50/51.- Phase overcurrent protection
∙∙ 50/51N.- Neutral overcurrent
protection
∙∙ 50/51SN.- Sensitive neutral
overcurrent protection
∙∙ Breaker Monitoring
∙∙ 74 TC/CC Trip and close circuit
supervision (optional)
∙∙ Opening, closure, kl2 counters
∙∙ Alarm for excessive number of trips
www.ingeteam.com
ingepac.info@ingeteam.com
Automatism
Measurement
OPTIONALS
∙∙ Command failure
∙∙ Opening and closure command
activated by pulse or by latch.
∙∙ Data Acquisition Functions
∙∙ Measurement log report (maximum and
minimum values)
∙∙ Event log
∙∙ Fault log
∙∙ Oscillographic log
∙∙ For each line: Measurement of
neutral and phase current, voltage
using resistive sensors, power (active,
reactive and apparent), power factor,
and frequency.
∙∙ Digital inputs and outputs
∙∙ Communications
∙∙ USB front port
∙∙ 2 Ethernet ports and 1 serial
∙∙ Slave/Server communication protocol:
IEC60870-5-104, IEC61850, DNP3,
PROCOME.
∙∙ Master/Client communication protocol:
MODBUS, IEC61850 “lite”
∙∙ Synchronisation
∙∙ SNTP
∙∙ Local Interface
∙∙ Keyboard (6 buttons for operating
switch up to 3 lines)
∙∙ Local/Remote and Manual/Automatic
∙∙ Web Server
∙∙ Remote monitoring or FW update
∙∙ TCP/Ip secure protocols (https,
sftp,ssh)
∙∙ LDAP Servers authentication