0EORDB/EORZDB 9EFORDB/EFORZDB0 pages
Model: 10EORDB/EORZDB
9EFORDB/EFORZDB
KOHLER Power Systems
Diesel
O9001
V#J KOHLER
POWER SYSTEMS
Generator Weights and Dimensions
Remote
Radiator
Inline
Radiator
Weight—dry, kg (lbs.) N/A
Length, mm (in.) 856 (33.7)
Width, mm (in.) 538 (21.2)
Height, mm (in.)
See the drawings on the last page for detailed dimensions.
Generator Ratings
259 (570)
965 (38.0)
553 (21.8)
572 (22.5) 620 (24.4)
Model
Series
Alternator Voltage Hz
Amps
25°C
(77°F)
kW/kVA
25°C
(77°F) Ph
10EORDB/
10EORZDB
4H4
120/240 60
120 60
41.7
83.3
10/10
10/10
9EFORDB/
9EFORZDB
4H4
110/220 50 40.9 9/9
115/230 50 39.1 9/9
220 50 40.9 9/9
240 50 37.5 9/9
RATINGS: All single-phase units are rated at 1.0 power factor. Mobile continuous ratings per ISO
3046 and ISO 8528-1. Obtain technical information bulletin (TIB-101) on ratings guidelines for
complete ratings definitions. GENERAL GUIDELINES FOR DERATING: ALTITUDE: Derate 1.0%
per 100 m (328ft.) elevation above 200 m (656ft.). TEMPERATURE: Derate 2.0% per10°C(18°F)
temperature above 25°C (77°F).
Availability is subject to change without notice. Kohler Co. reserves the right to change the design or
specifications without notice and without any obligation or liability whatsoever. Contact your local
Kohler® generator set distributor for availability.
Mobile/Commercial
Generator Set
Engine Features
Heavy-duty construction
Engine is compliant with the Environmental Protection
Agency (EPA) requirements
Water-cooled design
Diesel fueled
Three cylinders
Four cycle
Frequency regulation of ±2.5%
Electric fuel lift pump
Lifting eye
Generator Features
CSA certified, file #LR 955
US Testing approved
Remote start 12-pin connector
Class H insulation
Voltage regulation of ±1.5%
Radio suppression
Outstanding motor-starting capability
Sustained short-circuit capability
Four-point mounting with vibration isolators
Prototype-tested, factory-built, and production-tested
design
ADC 2100 Advanced Digital Control
Features
• Designed for today's most sophisticated electronics
• Easy to read alpha-numeric display
• Compact, integrally mounted control
• Potted boards/sealed connectors for maximum
corrosion protection
• SAE J1939 CAN bus output
• Remote monitoring of up to 13 fault conditions
• Membrane keypad for configuration and adjustment
• Programmed crank cycle
G3-42 (10EORDB/EORZDB) 5/13e
"