436 Series0 pages
436 SERIES
TRI-GAS ANALYZER FOR MONITORING
PURITY AND PURGING OF HYDROGEN
COOLED POWER GENERATORS
APPLICATIONS
For continuous analysis of hydrogen (H2) purity and for
purge monitoring of hydrogen-cooled generators and
synchronous converters.
FEATURES
• One analyzer monitors all 3 gases for purity (Range 1) or
purging (Ranges 2 and 3):
• Range 1: 0-100% H2 in Air
• Range 2: 0-100% H2 in CO2
• Range 3: 0-100% Air in CO2
• Bright digital readout
• 4-20 mA isolated output for 85-100% of H2 in Air
• Thermal-conductivity cell with high accuracy and
repeatability, cannot be burned out.
• Explosion-proof gas detector enclosure suitable for
Class 1 Division 1 Group BCD rated areas
• Fast response (T90 -10 to 15 secs)
• Built in pressure regulator
OPTIONS
• Isolated 4-20mA output for any range selected
• 2 levels of low H2 purity alarms & detector fail alarm
• Automatic Calibration by microprocessor control
available on N7MC configuration
• Serial output with data-logging software
• Oil vapor filter assembly
NEMA 7 Gas
Detector Cabinet
Choice of Control
Cabinet as follows:
NEMA 4 Control
Cabinet
or:
19" Rack Mount
Control Cabinet
or:
NEMA 7 Control
Cabinet
CALIBRATION
• Channel 1 - Air for Zero, 100% H2 for Span
• Channel 2 - 100% CO2 for Zero, 100% H2 for Span
• Channel 3 - 100% CO2 for Zero, Air for Span
NOVA ANALYTICAL SYSTEMS
www.nova-gas.com
Oil Vapor Filter Assembly
- protects analyzer from sensor
fouling caused by oil-vapors
from power generator