MX15_lit0 pages
Single Channel Controller
MX 15
Single Channel
Controller
Enclosure
Size
Material
Mounting
Cable entries
Protection
185 x 157 x 67 mm (W x H x D)
ABS
By DIN Rail supplied
3 cable-glands M20 (outer diameter 5.5 to 12 mm)
1 cable-glands M16 (outer diameter 4 to 8 mm)
IP31
Power Supply
230 or 115 VAC and 21 to 30 VDC
(nominal 24 VDC)
Consumption
20 VA
-10 to + 45°C
Operating temperature
Voltage
Cabling
Sensors
Terminal block
t On-board display
t DIN rail mounting provided
t 2 fully programmable alarms
t 3 on-board relays
Designed for use in boiler rooms and car
parks, the new MX 15 controller provides
the most cost effective solution for the
monitoring toxic or flammable gases and
vapors in ambient air.
Easy to install and operate, the MX 15
control unit combined with the OLC(T) 10
detectors provide a low cost solution for
light industrial applications.
Maximum
cable length
1 flammable gas detector OLC 10 or 2 detectors OLC 10
TWIN for detection of methane, butane, propane in boiler
rooms and LPG, Natural Gas for Vehicles or H2 in car parks
1 flammable gas transmitter OLCT 10 for detection of
methane, butane, propane in boiler rooms and LPG,
Natural Gas for Vehicles or H2 in car parks
1 to 5 similar detectors type OLCT 10 for detection of CO,
NO, NO2 in car parks for example
Signal / 2 : 0 V / 3 : + 24 VDC
OLC 10 (flammable only): 3-wire, shielded, core size 1 to
1.5 mm2, 300 m max
OLC 10 TWIN (flammable only): 4-wire, shielded, core size
1 to 1.5 mm2, 300 m max
OLCT 10 (flammable or SC): 3-wire, shielded, core size 1
to 1.5 mm2, 1 Km max
OLCT 10 (toxic): 2-wire, shielded, core size 0.75 to 1.5
mm2, 4 Km max
Display
Type
Visual
indications
Gas and unit
Keyboard
Alarms &
relays
Liquid Crystal Display, 4 digits and extra friendly symbols
4 DELs. Green: power on, Red: alarms triggered,
Orange: failure
Selectable in a programmed list
3 keys for access to main menu, test or acknowledgement
1 : Enter / Menu, 2 : - / test indicator, 3 : + / acknowledgement
2 programmable and independent levels, falling or increasing alarms, latching or unlatching modes, local or remote
acknowledgment
2 alarm relays normally energized, selectable normally open
or normally closed (de-energized on request at the factory)
1 fault relay, normally energized
Relay ratings : 2A at 250 Volts AC or 30 Volts DC
Approvals
www.oldhamgas.com
Category 3G (flammable gas detection metrology
EN 61779-1 and EN 61779-4)
Low Voltage Directive
EN 61010
Electromagnetic
Compatibility
(EEC directive)
The Fixed Gas Detection People
ATEX 94/9/CE
Directive
EN 50270
an
company
www.ist-group.com
"