500 kW Prefabricated Data Center Power Module0 pages
500 kW Prefabricated Data Center Power Module
Data Sheet
General
Output Capacity
Primary Bus /Critical
Bus
Up to 800kW Continuous
Up to 500kW or 475kW N+1 UPS
ATS
1600A 4 Pole Closed & Open Transitions
UPS Topology
Schneider Electric offers scalable, easy-to-deploy,
Prefabricated Data Center Modules.
Modular, Scalable Double Conversion Online
Climate Control
Fire Suppression
Efficiency at 100% Load
Air cooled, direct expansion with free
cooling; Optional humidity control.
IG541 (Inergen) fire extinguishing system
with smoke/heat detection, auto/manual
actuation, audible/strobe alarms
94%
Input
Input Power Voltage
(Nominal)
Grid System
+/- 10%, -6%
Frequency (Nom)
50 hZ
Maximum Input Current
1600A @ 400V
Power Factor
>.995% @ Full Load (UPS)
ITHD
Fire Suppression,
Alarms, Controls,
3 phases + neutral + PE
Voltage range
Wall Mounted
Air Conditioners
230 / 400V AC
5% at Full Load (UPS)
Output
Voltage
230/400V AC
Grid System
3 phases + neutral + PE
Voltage Regulation
<2% from 0 - 100% linear load
<6% full non-linear load per IEC//EN62040-3
Output Current
(Nominal)
Primary Bus 1600A Continuous
Critical Bus 722A Continuous
Battery System
Symmetra PX
500 kW UPS
Battery Type
VRLA – Long Life Battery Modules
Estimated Runtime
5mins @ Full Load
Cooling
Cooling Redundancy
Sensible Cooling
Capacity (nominal)
Sensible Heat Ratio
(SHR)
p
External Temperature
for Total Free Cooling
Refrigerant
N+1
36.6kW (N+1) @ 35°C, External Ambient
0.92
14° C
R407C
Physical
Length
13,000 mm
Width
3,000 mm
Height
3050 mm
Weight
Shipping: 21,840 kg
Operational: Up to 27,000kg
Stacking Containers
g
Switchgear
Optional
p
Environmental (external)
Operating min/max
temp.
Operating humidity
range
-20° to 50°C
0-100%
Operating Altitude
0 – 1000m
Audible Noise
(pressure)
<45 dB(A) @ 10m
Main Options
Uniflair CRACs
Additional Features
EMEA 500kW Prefabricated Data Center Power Module – PFMPE0500EB
Proximity keyless locks;
Load Bank Connection Breaker
Local HMI, Physical Surveillance cameras;
integrated power management system and
controls; Fiber port; Entry Locks; External
Extended Runtime Connection