Type FL Pressure Reducing Regulators0 pages
Bulletin 71.2:FL
nnnnApril 2012
nnnnType FL Pressure Reducing Regulators
nnnnFeatures
nnnn• No Atmospheric Bleed—Type FL eliminates nuisance
nnnnand wasteful bleed gas to atmosphere by utilizing a
nnnntwo-path pilot-operated control system, which bleeds
nnnn100% of the gas to the downstream system while the
nnnnregulator is operating.
nnnn• Quiet Operation—Optional noise abatement
nnnnsystems are available.
nnnn• Control Accuracy—Keeps constant inlet
nnnnpressures to downstream equipment by accurately
nnnncontrolling system pressures at widely varying flow
nnnnrates and supply pressures for maximum efficiency and
nnnnbest operation.
nnnn• Versatility—A wide variety of applications such
nnnnas natural gas transmission and distribution systems,
nnnnpower plants, monitors, and sour gas with inlet
nnnnpressures up to 1480 psig /102 bar.
nnnn• Easy In-Line Maintenance—With the optional
nnnnoutlet flange spacer, trim parts such as the disk holder
nnnncan be inspected, cleaned, and replaced without
nnnnremoving the body from the pipeline.
nnnn• Tight Shutoff—A combination of soft seat and
nnnnmetal plug with a knife edge creates the seal.
nnnn• Easy Startup—Equal inlet and outlet pressure
nnnnratings allow easier startup and shutdown.
nnnn• High Capacity—Up to NPS 10 / DN 250 body
nnnnsize, the body design and flow passage allows
nnnnexceptionally high capacities with a maximum
nnnnCg of 51,500 - 2:1 line size.
nnnn• In-Service Travel Indicator—The travel indicator
nnnnwith protective cover, responds to the precise movement
nnnnof the diaphragm and plug assembly and shows the
nnnnactual valve position.
nnnnIntroduction
nnnnType FL regulator is accurate, pilot-operated, pressure
nnnnbalanced, soft-seated regulator designed for high-pressure
nnnntransmission/city gate, large capacity distribution systems,
nnnnand power plant feeds. Type FL provides smooth and quiet
nnnnoperation, tight shutoff, and long service life. The regulator
nnnnutilizes a main valve actuator, a Type PRX pressure reducing
nnnnpilot, and a Type SA/2 pilot supply pressure regulator.
nnnnFigure 1. Type FL Regulator with Type PRX Pilot
nnnnType PRX pilot uses inlet pressure reduced by a Type SA/2
nnnnsupply pressure regulator, as loading pressure to operate the
nnnnmain valve actuator. The outlet pressure is sensed through
nnnna control line on the main valve actuator and also on the
nnnnType PRX pilot diaphragm.
nnnnThe regulator's superior performance is due to the amplifying
nnnneffect of the pilot and two-path control system. Changes
nnnnin outlet pressure act quickly on the actuator diaphragm
nnnnto provide fast response to system change. Then the pilot
nnnnamplifies any small system changes to position the main valve
nnnnfor precise pressure control.
nnnnType PRX Pilot Descriptions
nnnnA pressure reducing pilot that has the ability to handle a wide
nnnnrange of setpoints from 14.5 to 1160 psig /1.00 to 80.0 bar
nnnnin two versions:
nnnnType PRX/120: A pressure reducing pilot with an outlet
nnnnpressure range of 14.5 to 435 psig /1.00 to 30.0 bar.
nnnnType PRX/120 can be used as the pilot on single stage
nnnnpressure-reducing regulators or as the monitor pilot or as the
nnnnworking pilot in wide-open monitor systems.
nnnnC
nnnnO
nnnncn
nnnno
nnnnCD
nnnno
nnnnTARTAR/A/P
nnnnwww.tartarini-naturalgas.com
nnnnEMERSON.
nnnnProcess Management
"