Temperature0 pages
PID500/PID110/PID330
TEMPERATURE CONTROLLER
MODEL (Bezel Size)
Description
Features
Display
Inputs
Sampling Time
Resolution
Temperature Unit
Indication Accuracy
Main Output
Auxiliary Output
Retransmission Output
Control Action
Hysteresis
PID Parameter
Heat Cool PID
Alarms
Ramp Soak
Soft Start Time
Communication
(Optional)
Power Supply
Temperature
Humidity
Housing
Weight
Certification
Dimensions
PID500 (48 x 48)
PID110 (96x48)
PID330 (96 x 96)
Advanced PID Controller, Covers most applications.
Universal input, Auto tune, Selectable lower display,
Single point ramp-soak, Heat-cool PID, Soft start, Auto / manual mode
4 digit Upper display: Process value, 4 digit Lower display: Selectable.
Thermocouple: J, K, T, R, S, C, E, B, N, L, U, W, Platinel II RTD: Pt100, Signal Inputs (DC): -5 to 56 mV, 0 to 10 V, 0 to 20 mA
200 ms
TC/RTD : 1 / 0.1°; Analog input :1 / 0.1 /0.01 / 0.001.
°C/°F (selectable)
For TC inputs: 0.25% of FS. ±1°: For R & S inputs: 0.5% of FS. ±2° (20 min of warm uptime)
For RTD inputs: 0.1% of FS. ±1°: Cold junction accuracy ± 5°C ; Signal input: ±0.5%, ± 1 digit
Relay : 5 AO230V AC or 30V DC, or SSR drive voltage : 18V DC@20 mA or
Current: 0/4 to 20 mA DC (max load 500E) or Voltage: 0 to 5/1OV DC (min load 10K)
Max 2 (Relay or SSR drive voltage).
Mode : Set point or Alarm mode. Alarm operation: Absolute / Deviation / High / Low / Band, Sensor break.
0/4-20 mAor 0 - 5 V, orO - 10V DC (Main output is user selectable as control or retransmission output)
Autotune PID or ON - OFF, P, PI, PD, PID
0.1 to 99.9°
Proportional Band : 0.0 to 400.0°, Integral Time : 0 to 3600 sec, Derivative Time : 0 to 200 sec, Cycle Time : 0.1 to 100 sec
Control Method : PID, Cycle Time : 0.1 to 100 sec, Proportional Gain : 0.0 to 400.0°, Deadband : Programmable (SPLL to SPHL)
Modes : Deviation high/low, Absolute high/low, Band, Sensor break, Hysteresis : 0.1 to 99.9°
Ramp Rate : 1 to 9999°/hr, Soak Time : 0 to 1440 min
0 to 999 min
Interface Standard : RS485, Communication address : 1 to 99, maximum of 32 units per line, Transmission Mode : Half duplex,
Transmission Protocol: MODBUS RTU, Transmission Distance : 500m maximum,
Transmission Speed : 9600, 4800, 2400,1200, 600, 300 bits/sec
85 to 270V AC/DC (AC: 50/60 Hz)
Operating: 0 to 50°C. ; Storage:-20 to 75°C.
95% RH.
Flame retardant engineering plastic. (IP65 on front)
230 gms 330 gms
Refer diagram F on page 6 Refer diagram C on page 6
180 gms
Refer diagram A on page 6
Refer terminal diagram & ordering information on pg no. 5
www
selec.com
TC544A / TC244AX / TC344AX
TEMPERATURE CONTROLLER
PIC152N/PIC101N
PRECESS INDICATORS
Process Indicators
MODEL (Bezel Size) | TC544A (48x48) TC244AX (72 x 72) TC344AX (96 x 96) | TC533AX (48 x 48) | TC513AX (48x48) TC203AX (72 x 72) TC303AX (96 x 96) |
Display | 7 segment LED, dual display | 7 segment LED, Single display | |
Digits | 4 + 4 digits | 3 +3 digits | 3 digits |
LED Indications | Relay ON, Tune, Soak Time | Control output ON | |
Input Specifications | |||
Types | Thermocoupie (J,K,T, R,S) / RTD (PT100) | ||
Sampling time | 250 ms | ||
Resolution | 0.1/1° for TC/RTD inputs (fixed 1° for R & S type TC input) | Fixed 1° resolution | |
Temperature Unit | °C/°F selectable | ||
Indication Accuracy | For J, K&TTC inputs: 0.25% of F.S±1°, For R & S inputs: 0.5% of FS. ±2° (20 min of warm uptime for TC inputs), For RTD input: 0.1% of FS. ±1° | ||
Output Specifications | |||
Control Output | 1 | ||
Relay | 5A@250V AC / 30V DC, resistive | 10 A@250V AC or 30V DC, resistive | |
SSR | 12V DC, 50mA | ||
Auxiliary Output | 1 | ||
Relay | 5A@230V AC or 30V DC, resistive | ||
Functional Specifications | |||
Control Method | PID or ON/OFF | ||
Hysteresis | 0.1 to 99.9° | ||
Proportional Band | 1.0 to 400.0° | ||
Integral Time | 0 to 9999 sec 0.0 to 99.9 min | ||
Derivative Time | 0 to 9999 sec | 0 to 999 sec | |
Cycle Time | 0.1 to 99.9 sec | ||
Manual Reset Value | -19.9 to 19.9° | ||
Dwell (Soak) timer | OFF, 0 to 9999 min | ||
Heat - Cool PID | |||
Control Method | PID (with auto-tuning) | ||
Proportional Band-Cool | 0.0 to 400.0° | ||
Cycle Time-Cool | 0.1 to 99.9 sec | ||
Dead Band | |||
Alarm Modes | Deviation, Absolute | ||
Hysteresis | 0.1 to 99.9° | ||
Supply Voltage (AC: 50 or 60 Hz) | 85 to 270V AC/DC | 85 to 270V AC/DC | 85 to 270V AC/DC |
Temperature | Operating: 0 to 50°, Storage: -20 to 75° | ||
Humidity (non-condensing) | 95% RH | ||
Housing | Flame retardant engineering plastic. (IP65 on front) | ||
Weight | TC544A:142 gms TC244AX: 190 gms TC344AX: 252 gms | TC533AX:129 gms | TC513AX:129 gms TC203AX:180gms TC303AX: 240 gms |
Certification | ,^UL (RoHS applicable only for TC544A) | ||
Dimensions | TC544A: Refer diagram A on page 6 TC244AX : Refer diagram B on page 6 TC344AX : Refer diagram C on page 6 | Refer diagram A on page 6 | TC513AX : Refer diagram A on page 6 TC203AX : Refer diagram B on page 6 TC303AX : Refer diagram C on page 6 |
□ U £
St |
o a |
MODEL (Bezel Size) | PIC152N (48X96) | PIC101N (48X96) |
Description | 2 Alarm outputs with retransmission. | Low cost indicator (no output) |
Display | 4 digit, 7 segment LED : 0.56" | |
LED Indication | Alarm ON (2 Nos) | None |
Error Indications | Over range/Under range/Open sensor/TC reverse | |
Inputs | Thermocouple: J, K, T, R, S RTD:PT100 Signal Inputs (DC):-5 to 56 mV, 0 to 10V, 0/4 to 20 mA | Thermocouple: J, K, T, R, S RTD:PT100 Signal Inputs (DC): 0 to 56 mV, 0 to 10 V, 0/4 to 20 mA |
Resolution | Temperature input: 1/0.1"C / "F; Signal input: 0.001, 0.01, 0.1 & 1. | |
Accuracy | ForTC inputs: 0.25% of F.S. ±1°, For R & S inputs: 0.5% of FS. ±2° (20 min of warm up time forTC input), For RTD inputs: 0.1% of F.S. ±1°, For Signal inputs: ±0.5% of F.S., ± 1 digit | |
Alarms | 2 nos | |
Alarm Modes | High alarm, Low alarm, Band, Fail output and Fault diagnosis | |
Hysteresis | 0.1 to 99.9" | |
Annunciator | Programmable | |
Reset Action | Automatic or Latched | |
Relay Rating | 5A@ 250V AC or 24V DC | |
Retransmission Output | 0/4 to 20 mA DC, 0 to 5V DC, 0 to 10V DC | |
Sensor Supply | 24V DC, 30 mA | |
Supply Voltage AC: 50 or 60 Hz | 85 to 270V AC/ DC | |
Temperature | Operating:0 to 50"C. Storage:-20 to 75"C. | |
Humidity | 95% RH. | |
Housing | Flame retardant engineering plastic. (IP65 on front) | |
Weight | 240 gms | 200 gms |
Certifications | C€ .HE. a£ | C€ ,W. it |
Panel Cutout Size | Refer diagram E on page 6 | Refer diagram E on page 6 |
Refer terminal diagram on pg no. 5 & ordering information on pg no. 6
CH403
COOLING CONTROLLER
MODEL (Bezel Size) | CH403 (36 x 72) | ||
Display | 3 digit | Display Offset | -19.9to20.0°C/°F |
Control Modes | ON/OFF (Hysteresis-0.1 to 9.9°) | Restart Time Delay | Adjustable from 00 to 99 Min |
Sensor Range | NTC type sensor | Relay Action | Heat & Cool Mode |
Resolution | 1 /or | Defrost Time | Programmable from 00 to 99 Min |
Accuracy | ±1 % of F.S. | Defrost Frequency | Programmable from 00 to 99 (Hr/Min/Sec) |
Setpoint | 1 | Power Supply (AC: 50/60 Hz) | 85 to 270V AC/DC |
Output | Main Output: Relay, Alarm Output: Relay / SSR | Certification | C€ AH. |
Hysteresis | 0.1 to 9.9°C/°F | Panel Cutout Size | Refer diagram D on page 6 |
Refer terminal diagram & ordering information on pg no. 5
Refer terminal diagram on pg no. 5 & ordering information on pg no. 6
"