SEC 4855 Relay Module0 pages
SEC 4855
Relay Module
Features
•
•
•
•
•
•
•
Provides relay contacts at local or remote locations
Used in conjunction with Supervision Plus Software
Is wired in series with the SEC RS-485 data highway and 24 VDC power
Any number of SEC 4855’s can be connected to a single system
Relays can be programmed for global, individual point, fault or zone alarm conditions
Each relay is programmed for independent operation
Explosion proof or non-explosion proof models available
Operation
The SEC 4855 Relay Module is used with SEC Supervision Plus software to provide relay contacts at local or remote
locations. Each SEC 4855 Relay Module is assigned a unique identification number, allowing multiple modules to be
connected anywhere on the SEC network. SEC Supervision Plus continuously polls and updates the SEC 4855 Relay
Modules.
Each SEC 4855 Relay Module consists of one Control Board and either 1 or 2 Relay Boards depending on model selected.
The Control Board has 2 LED’s, one for Power and the other for Data Transmission. The Control Board communicates with
the SEC Supervision Plus software, activating the relays when the alarm conditions are present. The Relay Board consists
of 8 relays, 8 LED’s and the terminals for the field wiring connections.
The individual relay coils can be programmed (using SEC Supervision Plus) for normally energized or normally de-energized operation. The relays can be manually controlled or deactivated by SEC Supervision Plus. Programmable time delay
and latching/non-latching features are also standard with the SEC 4855 Relay Module.
The Control Board and the Relay Boards are connected together in an anodized aluminum bracket. The units are
suitable for mounting directly to an electrical enclosure panel, or can be purchased already mounted in various types of
enclosures.
Specifications
Part Number and Model Number
142-0155 - SEC 4855-8 with no enclosure
142-0156 - SEC 4855-16 with no enclosure
142-0199 - SEC 4855-8N with NEMA 4 enclosure
142-0200 - SEC 4855-16N with NEMA 4 enclosure
142-0201 - SEC 4855-8EX with explosion proof enclosure
Class 1, Div. 1, Groups B,C & D
Input Power
10-30 VDC
Relay Contacts
SPDT: 8 Amps @ 250 VAC
8 Amps @ 30 VDC
Output (digital)
RS-485 LAN
Weight
Approximately 6 lbs. (2.7 Kg)
© 06-99
"