Legacy Series 18 and 19 Universal Temperature/Process Controller0 pages
9408 Ath Legacy:Layout 1
12/17/08
11:48 AM
Page 4
Legacy Series 18 and 19
Universal Temperature/Process Controller
▲ Switch-Selectable Inputs
▲ User-Selectable Ramp to Setpoint
▲ Auto-Tuning, Heat or Cool
▲ Dual Output/Dual Alarm Capabilities
▲ On/Off Through Full PID Operation (P,PI,PD,PID)
▲ NEMA 4X (IP65) Dust and Splash-Proof
Front Panel
▲ Bumpless Auto/Manual Transfer
▲ Adjustable Hysteresis & Heat/Cool Spread
The Athena Legacy 18 and 19 Controllers are available as
1/8 DIN (18) vertical or 1/8 DIN (19) horizontal models. Both
panel mounted, auto-tuning controllers can be used for
precise control of a single loop with two independent
outputs. The controllers accept thermocouple, RTD, voltage,
or current input. RS-232 or RS-485 communications are
available, and two digital LED displays provide visual
indication of various controller functions.
▲ Field-Configurable Process, Deviation, or
Latching Alarms
▲ Optional Process Variable Retransmission
▲ Remote Setpoint Select, Non-Linear Inputs, or
Other Special Options
▲ cUL and CE Approvals
Ordering Information
1 8
1 9
Input
“E” TC
“E” TC
“J” TC
“J” TC
“K” TC
“K” TC
Platinel® II
Platinel II
“N” TC
“N” TC
“R” TC
“R” TC
“S” TC
“S” TC
“T” TC
“T” TC
100 ohm RTD
100 ohm RTD
100 ohm RTD
100 ohm RTD
1000 ohm RTD
1000 ohm RTD
1000 ohm RTD
1000 ohm RTD
1 to 5 V
0 to 5 V
10 to 50 mV
0 to 50 mV
4 to 20 mA*
0 to 20 mA*
0 to 10 Vdc
2 to 10 Vdc
0 to 1 Vdc
22
Range
0 to 1292° F
-18 to 700° C
0 to 1400° F
0 to 750° C
0 to 2460° F
0 to 1349° C
0 to 2372° F
-18 to 1300° C
0 to 2370° F
0 to 1300° C
0 to 3200° F
0 to 1750° C
0 to 3200° F
0 to 1750° C
-200 to 600° F
-100 to 300° C
-328 to 1562° F
-200 to 850° C
-199.0 to 450.0° F
-100.0 to 225.0° C
-328 to 1562° F
-200 to 850° C
-199.0 to 450.0° F
-100.0 to 225.0° C
Scaleable
Scaleable
Scaleable
Scaleable
Scaleable
Scaleable
Scaleable
Scaleable
Scaleable
Code
EF
EC
JF
JC
KF
KC
LF
LC
NF
NC
RF
RC
SF
SC
TF
TC
PF
PC
DF
DC
XF
XC
ZF
ZC
L1
L4
L2
L5
L3
L6
L7
L8
L9
Output 1
Code
0 = None
B = Relay, N.O.
C = Relay, N.O.,
without snubber
D = 0 to 7 mA
E = 0 to 20 mA
F = 4 to 20 mA
(500 ohm max)
G = 4 to 20 mA
(800 ohm max)
P = Pulsed 20 Vdc or 35 mA
S = Pulsed 20 Vdc or 17 mA
T = Solid-State Relay
V = 0 to 5 Vdc
X = 0 to 10 Vdc
Y = Relay, N.C.
Output 2
Code
0 = None
B = Relay, N.O.
C = Relay, N.0.
without snubber
D = 0 to 7 mA
E = 0 to 20 mA
F = 4 to 20 mA
(500 ohm max)
G = 4 to 20 mA
(800 ohm max)
P = Pulsed 20 Vdc
or 35 mA
S = Pulsed 20 Vdc
or 17 mA
T = Solid-State Relay
V = 0 to 5 Vdc
X = 0 to 10 Vdc
Y = Relay, N.C.
Alarm 1
Code
0 = None
B = Relay, N.O.
S = 24 V
T = Solid-State
Relay
Alarm 2
Code
0 = None
B = Relay, N.O.
S = 24 V
T = Solid-State
Relay
Communications
Code Athena+
0 = None
A = RS-232 Athena+
B = RS-485 Athena+
Option 1
Code
00 = None
Heater Break Alarm
(Requires Current Transformer)
HA = 5 to 60 A
Aux Output/PV Retransmit
PA = 4 to 20 mA
PB = 1 to 5 V
PC = 0 to 20 mA
PD = 0 to 5 V
Remote Analog Setpoint
SA = 0 to 5 Vdc w/ switch
SB = 1 to 5 Vdc w/ switch
SC = 0 to 20 mA w/ switch
SD = 4 to 20 mA w/ switch
SE = Switch only
SF = 0 to 10 Vdc w/ switch
Option 2
Code
0 = None
Transducer Excitation
1 = 10 Vdc
2 = 12 Vdc
3 = 15 Vdc
4 = 5 Vdc
Special Options
00 = None
Consult Factory