F-300, D-300, U-3000 pages
Blue-White
R
Industries, Ltd.
Pitot Tube Insertion Meters
Engineering and Technical Data
F-300
U-300
D-300
Clamp-on Insertion Mount
Dual GPM / LPM scale
F-300
U-300
Features:
Dual GPM/LPM scale printed on both sides of the meter.
1” through 8” pipe sizes.
Flow rates from 2 to 1900 GPM (8 to 7200 LPM).
Corrosion resistant 316SS or PTFE internal float materials.
One piece machined acrylic body.
Mounts to existing pipe. No unions or adapters required.
Models for mounting on horizontal or vertical pipe.
Mounting clamps and gasket included.
Specifications:
Pipe Requirements: ...... IPS inch pipe size (ASTM-D-1785)
Max. Psi (bar): ............... 150 PSI (10.3 bar) @ 70o F (21o C)
Fluid temp. range: ........ 32o to 110o F/ 190o F (88o C) @ 0 PSI
Ambient temp. range: ...32o to 110o F/ -10o to 43o C
Note: Temperature & Pressure ratings of meter only. Actual pipe rating may vary.
Full scale accuracy: .............. +/- 10%
Power requirement: .............. No power required
Enclosure: ............................. NEMA 4X (IP56)
Approximate shipping wt: ... 1”-4” units: 1 lb. (.45 kg)
6”-8”units: 2 lb. (.91 kg)
Materials of Construction:
Meter Body: ...........Cast Acrylic
Float: ......................Standard range models = 316SS
Low range models = PTFE
Gasket: .................. Neoprene
Pipe Clamp: ...........300 series Stainless Steel
Pitot screw: ...........1” thru 2” models only. 300 series stainless Steel
Installation Requirements:
Minimum Straight Pipe Length Requirements
Horizontal Mount
FLOW
30 inch (10 X 3”)
F-300 SERIES
12 inch (4 X 3”)
1-1/2 inch
15 inch (10 x 1.5”)
6 inch (4 x 1.5”)
6 inch
60 inch (10 x 6”)
MINIMUM
OUTPUT
LENGTH
24 inch (4 x 6”)
MINIMUM
INPUT
LENGTH
Minimum Outlet Pipe Length
MINIMUM
OUTPUT
LENGTH
No Vertical Mount
Mounting location
I.D.
U-300 & D-300 SERIES
MINIMUM
INPUT
LENGTH
No Horizontal Mount
FLOW
The meter is designed to withstand outdoor conditions.
F series meters must be mounted at the vertical (twelve o'clock)
position on horizontal pipe only.
U & D series meters must be mounted on vertical pipe only.
The pipe must be completely full of water at all times.
See the minimum straight length of pipe requirement chart above.
The meter can accurately measure flow from one direction only.
U-series meters measure upward flows only.
D-series meters measure downward flows only.
FLOW
Minimum Inlet Pipe Length
3 inch
FLOW
I.D.
MINIMUM
INPUT
LENGTH
Example of Minimum Straight Pipe Length Requirements
Nominal Pipe Diameter
FLOW
MINIMUM
OUTPUT
LENGTH
I.D.
The meter’s accuracy is affected by disturbances such as pumps,
elbows, tees, valves, etc., in the flow stream. Install the meter in a
straight run of pipe as far as possible from any disturbances. The
distance required for accuracy is 10 times the nominal pipe diameter
before the meter and 4 times the nominal pipe diameter after the meter.
Vertical Mount
FLOW
I.D.
MINIMUM
INPUT
LENGTH
MINIMUM
OUTPUT
LENGTH