RTU80 pages
Compact outstation with data logging and local control
RTU8
Typical RTU8 application
INTRODUCTION
The RTU8 unit is a compact outstation with data logging facilities
designed for use in the industrial environment.
The unit is designed in a very compact 108/162 mm wide module for
DIN-rail mounting (35 mm symmetrical ). Dimensions conform to DIN
43880 (used for circuit breakers) thus insuring easy installation in
standard installation panels and boxes widely available in the electrical
industry.
The RTU8 can be delivered with a built-in mains power supply and a
charger (with a battery monitor) for an external lead acid battery,
enabling the RTU to operate regardless of interruptions in the mains
supply.
The RTU8 has a number of integral inputs and outputs and further
I/O´s can be added via an expansion bus. The RTU8 is compatible with
the Brodersen Series 2000/4000 product range and thus a wide variety
of expansion modules can be easily connected to the unit by standard
cables.
The unit can be programmed to perform simple control sequences
using an IEC 1131-3 (PLC) programming language. The RTU8 includes
facilities for local data logging, the process values to be logged are
defined as part of the IEC 1131-3 application program. Programming,
setup and data transfer is achieved by using the IOTOOL32.
When connected to a GSM modem the RTU offer a simple SMS
message alarm option.
The Modbus RTU protocol is used for data transfer from the RTU8 to
a PC either directly or via Hayes compatible dial-up modem, GSM, or
radio modems.
VERSIONS/ORDERING CODES
RS232
Expansion
Mains supply
C
Battery 12V
L
0 1 2 3 4 5 6 7
In
C
0 1 2
C
8 9 10 11 12 13 14 15
C
In
8 9 10 11 12 13 14 15
3 4 5 6 7
A
Power System I/O
B
C
D
RTU8
0 1 2 3 4 5 6
C
0 1
7
C
Out
2 3 4 5 6 7
E
0
1
2
3
0
1
2
3
C
Rxd
162mm
Txd
24V
C
Input/output
8 digital input/8 digital output
16 digital input/16 digital output
32 digital input (10-30V DC)
8 digital input/4 analog input
16 dig. in./8 dig.out./4 analog in.
24 digietal input/12 relay output
Options
RTC and data logging
RTU8
N
UCR-28IO/RTU 21.D1
Type
UCR
Power supply
12V DC PS (not isolated)
Built-in mains PS 110-240V
Built-in PS and battery charger
110-240V
Built-in PS 24-48VDC
Loop supply
No loop supply
24VDC/200mA*
12VDC/400mA*
*)UCR-28IO only
Analogue input range
0-10V/0-20mA
4-20mA
0-5V
0-20mA
0-2V
UCR
8DIO
16DIO
32DI
12I
28IO
36IO
/RTU
0
1
2
3
0
1
2
D1
D2
D3
D6
D7
Digital input range (digital types only)
10-30VDC uni-polar
P1
30-60VDC uni-polar
P2
30-60VDC bi-polar
P3
40-72VDC uni-polar
P4
40-72VDC bi-polar
P5
10-30VDC bi-polar
P6
DI on modules with AI is always 10-30VDC uni-polar unless other is
specified.
40073/11_10