P90-3S 90kVA Single Phase Open Generating Set0 pages
www.FGWilson.com
P90-3S
Image for illustration purposes only.
Output Ratings
Ratings and Performance Data
Generator Set Model
Prime
Standby
230V, 50 Hz
82.0 kVA / 82.0 kW
90.0 kVA / 90.0 kW
240V, 60 Hz
90.0 kVA / 90.0 kW
99.5 kVA / 99.5 kW
Standby Rating
These ratings are applicable for supplying continuous electrical power (at
variable load) in the event of a utility power failure. No overload is
permitted on these ratings. The alternator on this model is peak
continuous rated (as defined in ISO 8528-3).
Standard Reference Conditions
Note: Standard reference conditions 25°C (77°F) Air Inlet Temp, 100m
(328 ft) A.S.L. 30% relative humidity.
Fuel consumption data at full load with diesel fuel with specific gravity of
0.85 and conforming to BS2869: 1998, Class A2.
Alternator manufactured for
FG Wilson by:
Leroy Somer
Alternator Model:
LLB3114H
Control Panel:
DCP-10
Heavy Duty Fabricated Steel
Circuit Breaker Type:
Prime Rating
These ratings are applicable for supplying continuous electrical power
(at variable load) in lieu of commercially purchased power. There is no
limitation to the annual hours of operation and this model can supply 10%
overload power for 1 hour in 12 hours.
Perkins® 1104C-44TAG2
Base Frame:
Ratings at 1.0 power factor.
Engine Make & Model:
3 Pole MCCB
Frequency:
50 Hz
60 Hz
Engine Speed: RPM
1500
1800
Fuel Tank Capacity:
218 (57.6)
litres (US gal)
Fuel Consumption: l/hr (US gal/hr)
- Prime
22.1 (5.8)
26.0 (6.9)
- Standby
(100% Load)
24.3 (6.4)
28.8 (7.6)
Available Options
FG Wilson offer a range of optional features to tailor our generator
sets to meet your power needs. Options include:
Upgrade to CE Certification
A wide range of Sound Attenuated Enclosures
A variety of generator set control and synchronising panels
Additional alarms and shutdowns
A selection of exhaust silencer noise levels
For further information on all of the standard and optional features
accompanying this product please contact your local Dealer or visit:
www.FGWilson.com
Dimensions and Weights
Length (L)
Width (W)
Height (H)
Dry
Wet
mm (in)
mm (in)
mm (in)
kg (lb)
kg (lb)
1374 (54.1)
1113 (2454)
1131 (2493)
1980 (78.0)
890 (35.0)
Dry = With Lube Oil
Wet = With Lube Oil and Coolant
Ratings in accordance with ISO 8528, ISO 3046, IEC 60034, BS5000 and NEMA MG-1.22.
Generator set pictured may include optional accessories.