Particulate Transmitter: EM 30T0 pages
Analyze, Optimize, Comply
Particulate Transmitter
Model EM 30T
Features & Benefits
Simple, Low Cost 2-Wire Installation
Prevent Emissions
n Plan Filter Maintenance
n Protect Downstream Equipment
n Keep a Clean Work Place
n Superior to Traditional Triboelectric
n
n
Made in USA
Overview
The model EM 30T is a reliable particulate emissions monitor and filter leak detector in a 2-wire loop powered transmitter
configuration. The loop powered design is ideal for direct connection to PLCs and data loggers.
The model EM 30T is available in a compact 1-piece version and a 2-piece configuration with remote electronics for high
temperature or high pressure applications. The 2-piece configuration is also beneficial for baghouse applications where
outlet ducts are difficult to access. The base model is designed for general maintenance planning and process protection
applications. Optional detection level upgrades enable low level monitoring and early warning filter leak detection.
Adjustable linear or logarithmic output ranges in absolute units enable simple setup without confusing sensitivity and gain
settings. A log scale output enables trending both the baseline emissions and the high dynamic peaks that are caused by
filter cleaning cycles and developing leaks. Observation of both baseline and peaks is essential to setting proper alarms.
Principle of Operation
The EM 30T employs a field-proven combination of charge induction and protected-probe technologies invented by
FilterSense. As particles flow near and around the probe, a minute current is induced. A DSP processes the signal
into an absolute output relative to particulate flow. A protective layer over the probe works in combination with inductionsensing to ensure reliable operation with conductive particulate, moist powders, corrosive gases and particulate buildup.
Maintenance is minimal and there is no need for an air purge.