LOADING
Non-Intrusive Capacitance Switch0 pages
نسخه متنی
"
"
witch-Tek | |||||||||||||||||||
Switch-Tek Non-Int Cap LP50 0510 DS2_2 | |||||||||||||||||||
Non-Intrusive Capacitance Switch | |||||||||||||||||||
Features (?f Level detection through plastic tank walls up to 1" thick Sensor mounting brackets are offered in common tank materials for adhesive or tack-weld install Specifications | |||||||||||||||||||
r | Tank mounting: Tank mat. comp.: Tank wall thick.: Accuracy: Repeatability: Dielectric range: Conductive range: Supply voltage: Consumption: Contact type: Contact rating: | ||||||||||||||||||
Non-intrusive Non-metallic < 1" (25 mm) ± 1 mm in water ± 0.5 mm in water > 10 constants > 100 micromhos 12-36 VDC 25 mA maximum (1) SPST relay 60 VA | |||||||||||||||||||
Contact output: Process temp.: Enclosure rating: Enclosure mat.: Conduit entrance: Bracket material: | Selectable NO/NC F: -40° to 176° C: -40° to 80° NEMA 4X (IP65) PSO Single, 1/2" NPT 1005: PP 5005: PVDF 6005: PE 3M adhesive / plastic thermal weld PP 4-conductor, #22 AWG (shielded) Standard: 10' (3m) Special order: 25' (7.6m) or 50' (15.2m) General purpose EN 61326 EMC EN 61010-1 safety | ||||||||||||||||||
Ci | |||||||||||||||||||
3͜C | |||||||||||||||||||
Bracket mounting: Cable jacket mat.: Cable type: Cable length: | |||||||||||||||||||
Description The general purpose non-intrusive capacitance level switch is a great choice for clean or ultrapure, aqueous based liquids with non-coating and/or scaling characteristics. Media examples include deionized water and hydrochloric acid. The 1A relay provides a reliable switch interface with remote devices such as a PLC, SCADA or alarm. The sensor mounts on the exterior wall of non-metallic tanks. | |||||||||||||||||||
Classification: CE compliance: | |||||||||||||||||||
Non-Intrusive Ordering | |||||||||||||||||||
LP50-I I005 | |||||||||||||||||||
Ordering Notes 1) Select the bracket that matches the tank wall material in your application. 2) Each sensor comes with one user specified bracket. Additional brackets may be ordered separately for multiple installation points: LP95-1001: PP bracket LP95-5001: PVDF bracket LP95-6001: PE bracket 3) To special order a 25' (7.6m) or 50' (15.2 m) sensor cable, place the cable length at the end of the part number (ie: LP50-6005-25'). 4) When conduit is not used, add the LM90-1001 Liquid Tight Connector to seal the sensor. | |||||||||||||||||||
Bracket material (1) (2) (3) 1 PP 5 PVDF 6 PE | |||||||||||||||||||
10500 Humbolt Street Los Alamitos, CA 90720 ■ www.flowline.com ■ T (562) 598-3015 ■ F (562) 431-8507 |