4829 Standard Voltage Transformers0 pages
4829
StandardInductive Dry – Type Nominal Voltage Transformer
These high accuracy Inductive Dry type voltage
transformers built with synthetic resin have been
designed to be used as a reference transformer for
voltage transformer measurement with Tettex or
another transformer measuring devices.
FEATURES AND BENEFITS
The transformer is equipped with different High voltage
resin isolated bars to modify the transformers ratio
(high Voltage winding), allowing a fast and easy
configuration of the nominal transformers.
Dry type, no isolating oil means no leakages
Highest accuracy in the market +0.005% + 0.5Min
Large measuring range 40%.....120%
Easy to work with, changing the ratio by plug and ply
a connector. No cable reconnection needed
Other output voltages can be supplied under request
APPLICATIONS
The programmable electronic voltage burden Tettex 3691
is mostly used by:
Manufacturer of current instrument transformers
Calibration laboratories
National Standards Laboratories
On-Site Testing of high voltage current instrument
transformers
TECHNICAL SPECIFICATIONS
Primary Voltage
Secondary Voltage:
Accuracy range:
Max. Load
Voltage Error:
Phase Angle:
Load:
Frequency range:
Test Voltage:
Weight
Temperature range
4829a
3–5 –6 –10–15-20-30-40 kV
120 V
(40%.....120%) x Un
1VA cos ß = 1,0
+ 0.005%
+ 0.5Min
Max. 15 VA
50 Hz or 60 Hz
1,5 x Un
205 kg
-5°C.....+40°C
1/2
4829b
2.4–4.2–4.8–7.2–8.4–12–14.4–24– 34.5 kV
100 V (other values to be defined)
(40%.....120%) x Un
1VA cos ß = 1,0
+ 0.005%
+ 0.5Min
Max. 15 VA
50 Hz or 60 Hz
1,5 x Un
205 kg
-5°C.....+40°C