TS20 - Plate heat exchanger0 pages
TS20
TS20-MFG
Plate heat exchanger
Applications
General heating and cooling duties. Heating by means of steam.
Standard design
The plate heat exchanger consists of a pack of corrugated metal plates with portholes for the passage of the two fluids between which heat transfer will take place.
The plate pack is assembled betweeen a fix frame plate and a movable pressure plate and compressed by tightening bolts. The plates are fitted with a gasket which seals the interplate channel and directs the fluids into alternate channels. The number of plates is determined by the flow rate, physical
properties of the fluids, pressure drop and temperature program.
The plate corrugations promote fluid turbulence and support the plates against differential pressure.
The plate and the pressure plate are suspended from an upper carrying bar and located by a lower guiding bar, both
of which are fixed to a support column.
Connections are located in the frame plate or, if either or both fluids make more than a single pass within the unit, in the frame and pressure plates.
Typical capacities
Liquid flow rate
Up to 190 kg/s, depending on media, permitted pressue drop and temperature program.
Water heating by steam
2.5 - 15 MW at a steam condensation temperature of 150°C
2.5 - 9 MW at a steam condensation temperature of 120°C
Plate types
TS20M plates
Frame types
FM, FG and FS