E180520 pages
Electronic
Pressure Switch
EDS 601
The EDS 601 is an electronic
two-channel pressure switch with
display and analogue output.
Its digitally adjustable switching points
and switching hystereses make it
particularly suitable for applications
requiring frequent change-overs or
accurate switch point setting.
The variety of setting parameters
ensures versatility for use in all control
and monitoring tasks in hydraulics,
pneumatics, process control and in
general test and control engineering
applications.
Special features:
t
Two-channel pressure switch with
change-over contacts
tAccuracy ≤ ± 1 % FS
t
4-digit LED display
t
Signal output 4 .. 20 mA or
0 .. 10 V selectable
t be installed as a pressure gauge
Can
or as a front panel mounted unit
t
Digitally adjustable parameters
t
Optional permanent display of the
switching point or of the pressure
peak value
t be set to display values in
Can
any unit of measurement e.g.: kN, kg,
psi, ...
Technical specifications:
Input datat
Measuring rangest
Overload pressurest
Burst pressures t
Mechanical connectiont
Torque valuet
Parts in contact with mediumt
Output datat
Accuracy to DIN 16086,t
Max. settingt
(display, analogue output)
Repeatabilityt
Temperature driftt
t
Analogue output (optional)t
Signalt
t
t
Switching outputst
Typet
Switching voltaget
Switching currentt
Switching outputt
Switching cyclest
t
Reaction timet
Ambient conditionst
Compensated temperature ranget
Operating temperature ranget
Storage temperature ranget
Fluid temperature ranget
markt
Vibration resistance to t
DIN EN 60068-2-6 (0 .. 500 Hz)t
Shock resistance to t
DIN EN 60068-2-29 (1 ms)t
Protection class to DIN 40050t
Other datat
Supply voltage t
Current consumptiont
Switch-on currentt
Displayt
t
Connection supply voltage / t
analogue outputt
Connection relay outputst
t
Housing materialt
Weightt
16; 40; 100; 250; 400; 600 bar
24; 60; 200; 500; 800; 1000 bar
200; 200; 500; 1000; 2000; 2000 bar
Threaded port G1/4 DIN 3852
20 Nm
Mech. connection: Stainless steel
≤ ± 0.5 % FS typ.
≤ ± 1 % FS max.
≤ ± 0.5 % FS max.
≤ ± 0.05 % FS / °C max. zero point
≤ ± 0.05 % FS / °C max. range
selectable:
4 .. 20 mAt
0 .. 10 Vt
ohmic resistance ≤ 400W
ohmic resistance ≥ 2 kW
2 relays with change-over contacts
max. 250 V
max. 2 A per switching output
max. 50 W / 400 VA
10 million without loadt
1 million with load
approx. 10 ms including electronics
-10 .. +70 °C
-25 .. +70 °C
-25 .. +80 °C
-25 .. +80 °C
EN 61000-6-1 / 2 / 3 / 4
≤ 25 g
t
≤ 100 g
IP 65
20 .. 32 V DC
approx. 120 mA
approx. 1.5 A (100 ms)
4-digit, LED, 7 segment, red,
height of digits 13 mm
DIN 43650 / ISO 4400
(3 pole + PE)t
DIN 43651
(6 pole + PE)
aluminium, anodised
approx. 300 g
Note: t Reverse polarity protection of the supply voltage, excess voltage, override
t
and short circuit protection are provided.
t
FS (Full Scale) = relative to complete measuring range
E 18.052.6/03.11