KEA 101 NSTR0 pages
Control unit for emergency gensets
KEA 101 NSTR
General
The automatic control unit KEA 101 NSTR is used in emergency
power supply plants without overlapping synchronisation. Complete generator protection is included. The additional relay unit
RZ 071-D of the KEA 070 series is included in the delivery.
The output relay function and the parameters can be set with
a PC. As the KEA 101 is the same size and is attached in the
same manner as its predecessors, it can be exchanged without
difculty.
The automatic control unit is simple to operate as it is operated
by using the keys on the control panel.
Functions
• Start-stop for Diesel and gas engine with checking of preliminary start-up conditions
• Sensors for mains and generator voltage, frequency and rotating eld (asymmetry)
• Generator current sensor: Overload, short-circuit, unbalanced
load and thermal overload (bimetal relay)
• 48 alarm signals, of which 19 alarms with programmable text
and actuation, 7 alarms (alarms 24-26 and 33-36) with programmable actuation
• Software for sprinkler operation
• For each analogue signal input, actuation of two alarms via
limits
• Two potential-free analogue signal outputs, e.g. for direct
actuation of speed controllers or other controllers
• Parameters can be set using the keys and the display or via a
bre optics or USB interface with the ParaWin software
• Data transfer to a central control system via a CAN bus interface
• CAN bus interface* to engine management
• Various enhancement options:
Modem, printer actuation, Probus coupling etc.
Hardware
•
•
•
•
•
•
•
•
•
Input for alternator D+ with pre-excitation for AC alternators
14 terminals for alarm contacts on the RZ 071-D
14 general control inputs on the RZ 071-D
12 relays on the RZ 071-D, 8 of which can be parameterised,
contact load:
2 relays max. 35 V, 20 A DC
10 relays 250 V AC, 6 A
Input for pick-up
Battery monitor
Four slots for analogue input-card modules
Two slots for analogue output-card modules
Two CAN bus interfaces
Optional functions
The hardware must be upgraded accordingly for the software
options listed below:
• Integration of the automatic control unit in telephone monitoring by means of an internal modem (analogue, ISDN, GSM)
• Connection to other systems via Probus, for example
• Event recorder with protocol and fault printout via an RS 232
interface
Hardware options
Free analogue signal inputs and outputs can be used as follows:
• Relay extension unit RZ 071-E:
15 relays on the RZ 071-E, 14 of which can be parameterised,
contact load 250V AC, 6 A
• 2 analogue signal outputs 0 20 mA or 0 10 V
• 4 analogue signal inputs, can be equipped for:
Temp. Sensors PT 100 / PT1000, 0-10 V DC, 0-20 mA,
NiCr-Ni
Temperature and pressure sensor from MotoMeter, VDO,
Noris
PTC thermistor for generator protection*
Measurement of battery charging current*
• Modem* (analogue, ISDN, GSM)
• Bus coupling units*, e.g. Probus
• Hardware clock with battery back-up*
Technical Data
• Device for panel mounting,
Dimensions (WxHxD): 260x170x100 mm
• Weight: approx. 2.2 kg, any installation position
• Protection type (built-in): IP 44
• Ambient temperature:
Storage -20°C ... +70°C
Operation 0°C ... +55°C
• Standards/regulations:
VDE 100/710
• Switchable power supply: 9..12..15 V DC or
14..24..35 V DC
* on request
Alfred Kuhse GmbH
An der Kleinbahn 39, 21423 Winsen
Tel.: +49 (0)4171 / 798-0
Fax: +49 (0)4171 / 798-117
E-Mail: kuhse@kuhse.de
http://www.kuhse.de
Subject to modication
Datenblatt_KEA101NSTR_de_uk02
Stand: 02/2007