HRP22-V0 pages
Tecchnical Datasheet 2.30-10.022-11-EN
Device description
HRP22-V Heating Control Processor
Heating Control Processor HRP22-V
Basic function
HRP22 -V
Date 2010-01-18
For the control, management, optimization and
monitoring of heating plants with boiler control or for a
remote heating plant.
Bus- and modem-capable.
A maximum of two heating cycles and pre-controls
possible.
Single knob operation and graphics, illuminated
display for the entry and query of all DDC data.
Extensions of the basic function with HRP software
menus such as optimization, room correction,
limit, Stand-by, boiler control, circulation pump, operating hours, heat amounts counting, pump blocking
protection.
With the inclusion of plant macros, the Heating Control Processor HRP is completely configured, the
accompanying HRP software menus are set, the parameters are adjusted and the inputs and output
signals are assigned as well.
the dialog guides the user through the plaintext-oriented menu technology.
Entry and query of the data in four priority levels by means of a code key.
Week and Annual program. trend value acquisition and display of important plant values.
Eight Heating Control Processors HRPs are administered on the HRP-LRP-Bus system for a total
distance of 1000 m.
The communication of all Bus participants among each other in the form of queries or the modification
of all parameter is integrated part of the Heating Control Processor HRP.
Direct connection to the BMS on the RS232 interface. For plants that are distantly removed from each
other, data transmission to the BMS by modem on the public telephone network is possible.
Important messages can also be sent to a mobile telephone with a modem (GSM-SMS-Service).
Unlimited data backup on power failure.
• PLC functions with flags, timer and time programs, freely parameterizable
• 6 analog inputs for actives measuring element KP10
• 1 analog input 0..10 V
• 3 binary inputs
• 2 analog outputs 0..10 V
• 6 binary outputs max. 6(3) A; 230 V AC or zero-voltage
• plastic housing fire-resistant, for switching cabinet mounting
• mains 230 V AC ± 10 % 50..60 Hz
• internal voltage source 24 V DC, 7 VA
Page 1/6
Kieback&Peter GmbH & Co. KG
Tempelhofer Weg 50
12347 Berlin/Germany
Telefon: +49 30 60095-0, Telefax: +49 30 60095-164
www.kieback-peter.de, info@kieback-peter.de