180 REOZJG0 pages
Model:
180REOZJG
190-600 V
Tier 3 EPA-Certified for
Stationary Emergency
Applications
Ratings Range
Standby:
Prime:
60 Hz
140--180
175--225
130--165
165--206
kW
kVA
kW
kVA
50 Hz
105--168
105--210
100--160
100--200
Generator Set Ratings
Alternator
4S12X
4S13X
Voltage
120/208
127/220
120/240
139/240
220/380
277/480
347/600
110/190
115/200
120/208
110/220
110/220
220/380
230/400
240/416
120/208
127/220
120/240
139/240
220/380
277/480
347/600
110/190
115/200
120/208
110/220
110/220
220/380
230/400
240/416
Ph
3
3
3
3
3
3
3
3
3
3
3
1
3
3
3
3
3
3
3
3
3
3
3
3
3
3
1
3
3
3
Hz
60
60
60
60
60
60
60
50
50
50
50
50
50
50
50
60
60
60
60
60
60
60
50
50
50
50
50
50
50
50
130_C Rise
Standby Rating
kW/kVA
Amps
155/190
538
160/200
525
155/190
466
180/225
541
140/175
266
180/225
271
170/210
204
132/165
501
140/175
505
144/180
500
132/165
433
105/105
477
132/165
251
140/175
253
144/180
250
180/225
625
180/225
590
180/225
541
180/225
541
164/205
313
180/225
271
180/225
217
156/195
593
164/205
592
168/210
583
156/195
512
110/110
500
156/195
296
164/205
296
168/210
291
105_C Rise
Prime Rating
kW/kVA
Amps
140/195
486
150/188
492
140/195
421
165/206
496
130/165
247
165/206
248
155/194
186
124/155
471
128/160
462
136/170
472
124/155
407
100/100
455
124/155
236
128/160
231
136/170
236
165/206
573
165/206
541
165/206
496
165/206
496
155/194
294
165/206
248
160/200
192
144/180
547
152/190
548
160/200
555
144/180
472
110/110
500
144/180
273
152/190
274
160/200
278
Diesel
Standard Features
D Kohler Co. provides one-source responsibility for the
generating system and accessories.
D The generator set and its components are
prototype-tested, factory-built, and production-tested.
D The 60 Hz generator set offers a UL 2200 listing.
D The generator set accepts rated load in one step.
D The 60 Hz generator set meets NFPA 110, Level 1,
when equipped with the necessary accessories and
installed per NFPA standards.
D A one-year limited warranty covers all systems and
components. Two- and five-year extended
warranties are also available.
D Alternator features:
d The unique Fast-Responset X excitation system
delivers excellent voltage response and
short-circuit capability using a rare-earth,
permanent magnet (PM)-excited alternator.
d The brushless, rotating-field alternator has
broadrange reconnectability.
D Other features:
d Kohler designed controllers for guaranteed system
integration and remote communication. See
Controllers on page 3.
d The low coolant level shutdown prevents
overheating (standard on radiator models only).
d Integral vibration isolation eliminates the need for
under-unit vibration spring isolators.
d Multiple circuit breaker configurations.
RATINGS: All three-phase units are rated at 0.8 power factor. All single-phase units are rated at 1.0 power factor. Standby Ratings: The standby rating is applicable to varying loads for the duration of a power
outage. There is no overload capability for this rating. Prime Power Ratings: At varying load, the number of generator set operating hours is unlimited. A 10% overload capacity is available for one hour in twelve.
Ratings are in accordance with ISO-8528-1 and ISO-3046-1. For limited running time and continuous ratings, consult the factory. Obtain technical information bulletin (TIB-101) for ratings guidelines, complete
ratings definitions, and site condition derates. The generator set manufacturer reserves the right to change the design or specifications without notice and without any obligation or liability whatsoever.
G5-401 (180REOZJG) 8/12a