20REOZDC0 pages
Model:
20REOZDC
Compact Diesel
Standard Features
D Kohler Co. provides one-source responsibility for the
generating system and accessories.
D The generator set and its components are
prototype-tested, factory-built, and production-tested.
D The generator set is CSA certified, file # LR 955.
D UL 2200 listing is available.
D The generator set engine complies with Environmental
Protection Agency (EPA) emergency stationary
emissions requirements.
D The generator set meets NFPA 110, Level 1, when
equipped with the necessary accessories and installed
per NFPA standards.
D A one-year limited warranty covers all systems and
components. Two- and five-year extended warranties
are also available.
D Four-point mounting with vibration isolators.
D The brushless, rotating-field alternator has broadrange
reconnectability.
D Voltage regulation of ±0.25%.
D Sustained short-circuit capability.
D Customer connection box with field-connection terminal
blocks.
D Single-side access.
D Weather and sound enclosures are available.
d Enclosures reduce sound levels and protect the
generator set from the elements, animal intrusion,
and unwanted entry.
d Enclosures have a fade-, scratch-, and corrosionresistant Kohlerr Power Armortcream beige
automotive-grade textured finish and lockable, flushmounted door latches.
d See specification sheet G6-96 for enclosure features
and specifications.
Shown with available subbase fuel tank.
Generator Set Ratings
130 _C Rise
Standby Rating
105 _C Rise
Prime Rating
Hz
60
Ph
1
kW/kVA
Amps
kW/kVA
Amps
20/20
83.3
18/18
75.0
60
3
20.0/25.0
69.5
18.0/22.5
62.6
120/240
60
1
16.5/16.5
68.8
14.9/14.9
61.9
120/240
60
3
20.0/25.0
60.2
18.0/22.5
54.2
127/220
60
3
20.0/25.0
65.7
18.0/22.5
59.1
139/240
60
3
20.0/25.0
60.2
18.0/22.5
54.2
220/380
60
3
20.0/25.0
38.0
18.0/22.5
34.2
277/480
4J7
Voltage
120/240
120/208
Alternator
4H7
60
3
20.0/25.0
30.1
18.0/22.5
27.1
RATINGS: All three-phase units are rated at 0.8 power factor. Standby Ratings: Standby ratings apply to installations served by a reliable utility source. The standby rating is applicable to varying loads
for the duration of a power outage. There is no overload capability for this rating. Ratings are in accordance with ISO-3046/1, BS 5514, AS 2789, and DIN 6271. Prime Power Ratings: Prime power ratings
apply to installations where utility power is unavailable or unreliable. At varying load, the number of generator set operating hours is unlimited. A 10% overload capacity is available for one hour in twelve.
Ratings are in accordance with ISO-8528/1, overload power in accordance with ISO-3046/1, BS 5514, AS 2789, and DIN 6271. For limited running time and base load ratings, consult the factory. Obtain
the technical information bulletin (TIB-101) on ratings guidelines for the complete ratings definitions. The generator set manufacturer reserves the right to change the design or specifications without notice
and without any obligation or liability whatsoever. Contact your local Kohlerr generator set distributor for availability. GENERAL GUIDELINES FOR DERATING: ALTITUDE: Derate 0.8% per 100 m
(328 ft.) elevation above 200 m (656 ft.). TEMPERATURE: Derate 6.0% per 10_C (18_F) temperature above 25_C (77_F).
G5-376 (20REOZDC) 5/14d
"