RCD Testers
SPECIFICATIONS
ELECTRICAL
Supply Voltage: 240 Volts AC, 50/60Hz
Test Currents
I, Full Trip
Settings:
I/2, Half Trip
Settings:
6mA – 10mA – 30mA –
100mA – 300mA – 500mA
3mA – 5mA – 15mA –
50mA – 150mA – 250mA
FAST Trip Setting: 150mA (Applicable to Full
Trip Settings of 6, 10 and 30mA only)
Accuracy: ± 3% at 240V AC Supply Voltage
Rising Linearly To ±9% at ± 6% of 240V Supply Voltage
the16th Edition of the IEE Wiring Regulations.
Timing Range: 0 to 1999 mSec in steps of 1mSec
Timing Accuracy: ±2% of reading ± 1 digit
Test Current Duration:
½
2 seconds
I
0.5 or 2 seconds selectable
FAST
0.05 seconds
Fuse: 1amp, HBC, ceramic, 5 x 20mm
Transient Protection: VDR at input
Safety: EMC: Meets BS EN 50081-1, BS EN 50082-1
LVD: Meets BS EN 61010-1
The tester is designed to test the most common RCDs in
MECHANICAL
use,with a selector switch providing Fast, I and ½ Trip current
Height: 54mm (Excluding knob)
Length: 190mm
Width: 90mm
Case Material: Top – ABS
Base – ABS
Window – Polycarbonate
Weight (less carry case): 0.35 Kg
Display: Liquid Crystal
Sockets: CEE 22 (IEC 320)
Mains Lead: 1.5 metres long
The Digital RCD Tester is ideally suited for the testing of
Residual Current Protection Devices, in compliance with
settings. The Fast setting provides 150mA trip current for
RCDs not exceeding 30mA. The I setting provides full rated
trip current, which should cause the RCD under test to
trip.The ½ setting provides half the rated trip current
whereby the RCD should not trip. This tester has a 6mA
setting, widening the range of RCDs it can test.
Other features include a polarity switch with 0° and
180°settings which permits a test cycle to commence with a
positive or negative going wave form from the zero crossover point. The facility to establish whether the system under
ENVIRONMENTAL
test is correctly wired is provided by means of neon lamps
Operating Temperature Range: 0°C to +40°C
Humidity: 95°RH at 40°C
Storage Temperature Range: –20°C to +70°C
and monitoring of the voltage present on the earth
terminal.
Due to policy of continuous development, Martindale Electric reserves the right to alter equipment specification and description outlined in this document without prior notice. No part of
this document shall be deemed to be part of any contract for the equipment unless specifically referred to as an inclusion within such contract. © Martindale Electric Co. Ltd. 2005
Martindale Electric Company Ltd.
Metrohm House, Penfiold Trading Estate, Imperial Way, Watford, WD24 4YY. Tel: 01923 441717 Fax: 01923 446900
E-mail: sales@martindale-electric.co.uk Web site: http://www.martindale-electric.co.uk