Lighting arresster0 pages
72.5KV/123KV/120KV LIGHTING ARRESSTER
1.Type:YH10W-123KV
2. Service system voltage: 110 kV
3. Max system Voltage: 123 kV
4. Rated voltage : 96 kV
5. Nominal discharge currents (8/20 u S): 10 kA
6. Max. Continuous operation voltage : 77 kV
7. High current impulse (4/10 \i s): 100 kA
8. Energy absorption capacity: 4.5 kJ /kV Ur
9. Residual voltage (impulse 8/20 us- Discharge current 10
-kA crest): 256 kV
10. Line discharge class: 2
11.IEC60099-4
19. Type: YH10W-120/295
20. Rated Voltage: 120KV
21. Continuous Operating Voltage: 96KV
22.1/5 u s Steep Impulse Current Residual Voltage: 330KV
23.1/5 u s Lighting Impulse Current Residual Voltage: 295KV
14. Nominal discharge currents (8/20 u s): 10 kA 24"30/60 M SwitchinS lmPulse Current Residual volta9e: 280KV
25. 2ms A Suare Wave Impulse Withstsand Current: 700KA
26. High Current Impulse: 100KA
27. Lighting Impulse Withstand Voltage: 650KV
28. Power Frequency Withstand Voltage: 275KV
29. Creepage Distance: 3550mm
30. Standard: IEC60099-4
12. Type:YH10W-72.5KV.
13. Max Service system voltage : 72.55kV
15. Residual voltage (LIWL 1.2/50 u s): 192 kV
16. Energy absorption capacity: 4.5 kJ /kV Ur
17. Line discharge class: 2
18. Standard: IEC-99-4