Toc30A0 pages
APPLICATION
1-t Hofe-r^ a.
7
UK
Design
And Manufacture
Sensors
TOC-30A
Series Gas Detectors
TOC-30A Series Gas Detectors provide accurate
measurement of the background atmosphere to
measure for a specific hazardous target gas. Clean
lines and easy integration into existing or newly
planned control systems make the TOC-30A the
safety engineers device of choice. Using the latest
microprocessor addressable technology and software
TOC-30A is a reliable long term monitoring solution.
TOC-30A is supplied pre-calibrated ready to use.
Features
Standard 2 Gang Pattress Mount
Addressable Interface
Dado Mount or Wall Mount
Pre-calibrated
In-Service Calibration Possible
Replaceable Sensor
Order Codes
Standard Specifications
Power 18-28V DC (Loop Powered)
Construction ABS
Output 4 Wire Addressable
General Accuracy +1-2% of Range
Temperature -5 to 55 Deg C
Humidity 5-95% RH Non-Condensing
Sealing IP54
Weight 425g
Typical applications:
Commercial Kitchens
Lab's and Classrooms
Plant Rooms
HVAC Applications
Gas | Standard Range | Order Code | Typical Cell Life |
Flammable Gases external sensor | 0-100% LEL | TOC-31A-PHC | >3 Years |
Flammable Gases internal sensor | 0-100% LEL | TOC-30A-PHC | >3 Years |
Carbon Monoxide | 0-100ppm | TOC-30A-CO | >5 Years |
Oxygen | 0-30% Vol | TOC-30A-O2 | >5 Years |
Nitric Oxide | 0-200ppm | TOC-30A-NO | >2 Years |
Nitrogen Dioxide | 0-20ppm | TOC-30A-NO2 | >2 Years |
Ammonia | 0-100ppm | TOC-30A-NH3 | >2 Years |
Chlorine | 0-20ppm | TOC-30A-CL2 | >2 Years |
TOC-30A-Version
i.mm=i=MuaBt
International Gas Detectors
o£<=>
CH4
Pepper Road
Bramhall Technology Park
Stockport
SK7 5BW
England
Tel: +44(0)161 483 1415
Fax:+44 (0) 161 484 2345
Email: sales@internationalgasdetectors.com
Website: www.internationalgasdetectors.com
ISO >A l : MOO
sira
023827