Detuned reactors, 400V, 3INPP0 pages
reactors
Detuned Reactors
400V SERIES, TYPE 3INPP
12,5 kvar
25 kvar
50 kvar
REACTOR SERIES FOR HARMONIC FILTERING
- High quality materials
- Design optimised to reduce total losses
- Small mechanical size
- Low noise level due to the glued air caps
Technical specifications
Ambient
temperature
Protection class
IEC60289, IEC60076, VDE 0532,
UL/Ur file E202612, RoHs, CE
Standards
Ironcore multible aircap, low loss
grain oriented steel
Design
Tolerance,
Inductance
Installation
Color
-3/+3%
Linearity/%
1,75 x In 95% inductance
Insulation level
4 kVac
Temperature class
F 155 °C 6,25-12,5 kvar /
H 180 °C 25-75 kvar
Cooling
Noise level
Natural cooling
Used for
rated
capacitors
Q/kvar
6,25
12,5
25
50
75
25
50
Net
U/V
400
400
400
400
400
400
400
f/Hz
50
50
50
50
50
50
50
Optional
L/mH
6,14
3,07
1,53
0,77
0,51
3,30
1,65
I50 /A
I150 /A
14,09
19,80
39,70
79,40
119,10
I250 A/
I350 /A
4,77
6,70
13,40
26,80
40,30
Irms /A
1,71 10,55
2,40 21,10
4,80 42,20
9,70 84,40
14,50 126,60
Filtering factor fres 134Hz P14
56,40
113,00
2,62
5,23
5,35
10,67
2,66
5,30
IP00
Screw fastening
Light brown or black
Max. 50 dB with rated harmonics
currents at 1 m distance
• emperature switch 130-150 °C +-5%,
T
250 Vac (<6,3A)..500 Vac (<2A)
• tranded wire outputs
S
(flexible cable 110 °C)
• ateral mounting
L
Filtering factor fres 189Hz P7
0,48
0,70
1,40
2,70
4,10
- 20 ... +60 °C T60
40,00
80,00
Cu / Al
Weight
(kg)
Linearity
/%
Loss P h
tot
175
175
175
175
175
38
68
105
152
248
Cu
Cu
Al
Al
Al
175
175
158
255
AI 4,19
AI 7,90
0,89
1,45
1,83
4,52
7,68