In Head Temperature Transmitter with HART UP2000 pages
Data sheet
Date
Page
UP200
05/2012
1 of 2
IN HEAD TEMPERATURE TRANSMITTER WITH HART
UPLINK 200
OUTPUT CURRENT PRESET
For ease of system calibration and commissioning the
output can be set to a pre-defined level anywhere within
the (4 to 20) mA range.
Hart® Registered trademark of the HART
communication Foundation.
The UP200 has the HART communications protocol
which allows the user to quickly and easily download information or interrogate the device enabling
the following:
•
•
•
•
•
Simple re-ranging of the sensor type and
range.
Easy on site re-calibration.
Operation
with
proprietary
software
packages such as AMS Plant Web™ and
Conerstone™
Remote configuration on the 4 to 20) mA
loop with hand held communicator or with a
PC & HART modem
Online Digital communication concurrent
with a (4-20) mA Analogue signal.
In head transmitters can be applied in all areas of
process automation. They make sure that the
transmitted process temperature is both accurate
and secure. It also means that the sensitive sensor
cables no longer need to be connected to the
control system.
ATEX 94/9/CE
SPECIFICATIONS @ 20º C
Input Types Pt100, Thermocouple, mV or Slidewire.
(Ni100, via Custom[X]*¹ facility)
Time Constant (Filter off) 0.5 s (to 90 % of final value)
Filter Factor Off/ selectable between 1 s and 32 s or
Adaptive
Warm-up Time 120 s to full accuracy
Input/Output
Breakdown Isolation 500 VAC
ENVIRONMENTAL
Operating Range (-40 to 85) °C
Storage Temperature (-50 to 85) °C
Humidity Range (0 to 95) % (non condensing)
APPROVALS
EMC
BS EN61326
Hazardous Area ATEX II1GEExia IICT4-T6
FM
FM3610-IS/I/1/ABCD/T4
OUTPUT
Maximum Output Load [(Vsupply-10)/21.5] KI, 250 I
minimum loop load. Supply voltages over 30 V a
minimum loop load of 500 I is necessary.
Burnout Levels Low 3.75 mA, High 21.5 mA
Input Out of Range Low 3.8 mA, High 20.5 mA
Output Range (4 to 20) mA, Min. 3.75 mA,
Maximum 21.5 mA
Accuracy ± 5 LA
Thermal Drift 1 LA/ °C
Supply Voltage (10 to 40) VDC
Supply Voltage Effect 0.2 LA/ V
Hart TrimDac function available.
ENHANCED FEATURES
ENCLOSURE
Material ABS
Flammability SEI UL94-V0
USER CALIBRATION
In addition to sensor referencing, user offset and current
output trimming is possible via the HART commands.
MECHANICAL
Weight 43 g
CUSTOM LINEARISATION
The [X]*¹ facility allows the UP200 to be programmed
with a custom linearisation to suit non standard sensors
or sensors with unusual or unique characteristics.
SENSOR BURN OUT DETECTION
If any sensor wire is broken or becomes disconnected
the UP200 output will automatically go to its user
defined level (upscale or downscale). This happens
irrespectively of which wire is broken.
INPUT SENSORS & RANGES
Pt100 (RTD) 2, 3 or 4 Wire
Sensor Range (-200 to -850) °C
(18 to 390) I
Minimum Span 25 °C
Linearisation BS EN 60751, BS 1904, DIN
43760, JIS1604, CUSTOM [X]*¹
Max Lead Resistance 50 I per leg (balanced for 3 wire)
Basic Measurement Accuracy*²
0.01 % FRI*³ ± 0.07 % rdg
RTD Excitation Current (300 to 500) LA
Thermal Drift
Zero 0.008 °C/°C
Span 0.01 %/°C
THERMOCOUPLE
_______________________________________________________________________________________________
PCI (Process System Solutions) Ltd, Unit 7 Slaidburn Crescent, Southport, Merseyside, PR9 9YF, UK,
Tel: +44 (0) 1704 509090, Fax: +44 (0) 1704 509091,
email: sales@pci-instruments.com, Website: www.pci-instruments.com
(Specifications are subject to change without notice)