In Head Temperature Transmitter UP1000 pages
Data sheet
Date
Page
UP100
10/2013
1 of 1
IN HEAD TEMPERATURE TRANSMITTER
UPLINK 100
ENVIRONMENTAL
Ambient operating range:
(-40 to +85) °C
Ambient storage temperature:
(-50 to +90) °C
Ambient humidity range: 10 to 90% RH non
condensing
APPROVALS
EMC - BS EN 61326
ANNEX A
The UP100 is a cost effective “smart” transmitter
that accepts resistance signals including RTD
sensors and converts them to a standard industrial
(4 to 20) mA transmission signal over a programmed
range.
In head transmitters can be applied in all areas of
process automation. They make sure that the
transmitted process temperature is both accurate
and secure. It also means that the sensitive sensor
cables no longer need to be connected to the
control system.
ATEX 94/9/CE
TECHNICAL CHARACTERISTICS
Sensor Connection: 2 or 3 wire Screw terminal
Minimum span: 25 °C
Thermal Drift: 25 ppm / °C
Excitation current: <200 uA
Lead Resistance effect: 0.002 °C / Ohms
Maximum lead Resistance: 20 Ohms per leg
OUTPUT
Output Type: 2 wire 4 to 20 mA current loop
Output range: (4.0 to 20.0) mA
Output Connection: Screw Terminal
Output Limits: 3.8 to 21.5 mA
Accuracy:(mA output /2000) or 5 uA (Whichever is the
greater)
Loop Voltage effect: 0.2 uA / V
Thermal drift: 1 uA / °C
Maximum output load:
(Vsupply-10)/20] K Ohms
(Example: 700 Ohms @ 24V)
ANNEX F
IEC 61000-4-2
IEC 61000-4-3
IEC 61000-4-4
IEC 61000-4-5
Note - Sensor input wires to be less than 3 metres to
comply.
Construction acc. to ATEX 94/9/EC (on request)
Ex approval:
KEMA 10ATEX0003 X......................... II 3 GD Ex nA
[nL] IIC
T4...T6 or
II 3 GD Ex nL IIC
T4...T6 or
II 3 GD Ex nA [ic] IIC
T4...T6 or
II 3 GD Ex ic IIC
T4...T6
OPTIONS AND ACCESSORIES
•
•
Fitted inside a RDT terminal head
IS Version
HOW TO ORDER
Please specify: model, range, options if any
Example : UP100, -50 to 250 Deg C
SIDE VIEW
GENERAL SPECIFICATION
Update time: 300mS
Response Time: 400mS
Start up time: 4 seconds ( I out < 4 mA during start up)
Warm-up time: 1 minutes to full accuracy
Power Supply: (8 to 30) Volts dc
PHYSICAL
Dimensions: 43 mm diameter; 21mm height
Weight: 31 g (encapsulated)
Electrical equipment for
measurement control and
laboratory use.
Immunity test requirements
for equipment intended for
use in industrial locations
Test configurations,
operational conditions and
performance criteria for
transducers with integrated
or remote signal conditioning.
Electrostatic discharge
EM Field
Transient Burst (output)
Surge (output)
BASE VIEW
Ø 43.0 mm
33.0 mm
CENTRES
21.0 mm
Fixing holes 2 x Ø5.5 mm
Centre hole Ø4.0 mm
_______________________________________________________________________________________________
PCI (Process System Solutions) Ltd, Unit 7 Slaidburn Crescent, Southport, Merseyside, PR9 9YF, UK,
Tel: +44 (0) 1704 509090, Fax: +44 (0) 1704 509091,
email: sales@pci-instruments.com, Website: www.pci-instruments.com
(Specifications are subject to change without notice)