AS0 pages
Pressure Transmitter AS
Æ
27
118
20
ü
Potentiometers for zero and span
adjustment
ü 0.4%
Accuracy
ü
Measuring ranges: 0 ÷ 1, 0 ÷ 2.5, 0 ÷ 6
0 ÷ 10, 0 ÷ 16, 0 ÷ 25 bar
üsignal 4 ÷ 20 mA or 0 ÷ 10 V
Output
ü connection G1/2" or M20×1.5
Process
Load resistance R 3
5 kW
(f or supply out put)
Operating conditions
Operating temperature range (ambient temp.) –25 ÷ 80°C
Medium temperature range:
25 ÷ 120°C – direct measurement
25 ÷ 170°C – measurement using a impulse line
The transmitter is not heavy, so it can be fitted on
the installation. For pressure measurements of
steam or other hot media a si phon or impulse line
should be used. The needle valve placed u pstream the transmitter simplifies installation p rocess and enables the transmitter re pla cemen t.
Ordering procedure
Electrical diagrams
I/ 16
or G1/2"
10.5 ÷ 3 6 V DC – two wire transmission
15 ÷ 30 V DC – three wire t ransmission
24 V AC
Usup[V ] 10.5 V
Load resistance R[ W
]L
(f or current out put )
0.02 A
Installation
or 24 V AC (with
ADP-1 connector)
4 ÷ 20 mA, two wire tran smission
0 ÷ 10 V, three wire transmission
Power supply
Construction
15 ÷ 30 V DC
IP-65
00H17N14M2 (316 Lss)
0H18N9 (304ss)
Electrical parameters
Output signal
The acti ve sensing element is a piezo resistant
silicon sensor separated from the medium by a
diaphragm and by special ly selected type of
manometric liquid. The electronics are placed in
the casing wi th a degree of protection IP65. Electrical connection is the connector DIN 43650.
1
0.4%
0.05%
4 × range
0 ÷ 70°C
0.2% / 10°C
0.5% / year
Technical data
Degree of protection
Material of wetted parts
Material of casing
Application
0 ÷ 10 V
M20×1.5
Metrological parameters
Ac curacy
Hysteresis, repeata bilit y
Overpressure limit
Thermal compensation range
Thermal error
Long-term stability
The pressure transmitter AS is applicable to
measurement the pressure of gases vapours and
liquids. It may be applied in wa ter supply systems
and heat engineering.
3
3
SW27
Electrical connector DIN 43650
PG-11 Packing Gland
2
1/2’’ NPT M.
Æ
4
8
AS /___/___/___
2
4 ÷ 20 mA
3
1
+
Power
supply
–
Measuring range:
0 ÷ 1, 0 ÷ 2.5,
0 ÷ 6, 0 ÷ 10, 0 ÷ 16,
0 ÷ 25 bar
Process connection
1/2’’ NPTM, G1/2"
M20×1.5
Output signal:
4 ÷ 20 mA or 0 ÷ 10 V