Process Controllers P16111000 pages
Process Controller P1611100
0 to 10 VDC or 0/4 to 20mA Input
DC–
DC+ VOLTAGE
DC+ CURRENT
9
10
10V
20mA
Indicators
8
COMM
VOLTAGE AND CURRENT:
Specification
Displayt
The Model P161100 Controller accepts either a 0 to
10 VDC or 0/4 to 20 mA DC input signal and provides
accurate output control to maintain a process at a
set value.
Dual 4-digit displays allow viewing of the process
value and set-point simultaneously. Front panel
indicators show the control and output status. The
PID programming or On/Off control allows these
controllers to meet a wide variety of application
requirements.
Input
input Range
Accuracy
Impedance
Max.
Continuous
Overload
Resolution
0 to 10 VDC
(-1 to 11)
0.30% of
reading
+0.03V
1 MΩ
50 V
10 mV
0 to 20mA
(-2 to 22)
0.30% of
reading
+0.04mA
10 Ω
100 mA
10 µA
2 Line by 4-digit, LCD negative image transmissive with
backlighting
Top (Process) Displayt
7.6 mm high digits with red
backlighting
Bottom (Parameter) Displayt
5.1 mm high digits with green
backlighting
Annunciators
Status Annunciators:
O1t
Main control output is active.
O2t
Cooling output is active (when Alarm 2 is used for cooling)
A1t
Alarm 1 output is active
A2t
Alarm 2 output is active
°F, °C t
Temperature units
%PWt
Output power percentage is shown in Bottom display
MANt
Controller is in Manual Mode
Rt
Ramping Setpoint indicator
%t
Percent indicator
Display Messages:
OLOLt
Measurement exceeds + sensor range
ULULt Measurement exceeds - sensor range
SENSt
Measurement exceeds controller limits
ddddt
Display value exceeds + display range
-ddd t
Display value exceeds - display range
Powert
85 to 250 VAC, 50/60Hz, 8 VA
Control and Alarm Outputs
Relay Output
Typet
Form A
Contact Ratingt
3 A @ 250 VAC or 30 VDC; 1/10 HP @ 120 VAC
(inductive load)
H&B Sensors Ltd | Odyssey House | Durban Road | Bognor Regis | West Sussex | PO22 9RH | United Kingdom