42 series - Process Analysers0 pages
42 series
The 42 series developed by
Chemitec is dedicated to the
water treatment and industry
sectors, and enables the
following parameters to be
measured:
► pH/REDOX
► Dissolved oxygen
► Conductivity
► Turbidity
► Suspended solids
► Chlorine
► Chlorine dioxide
► Ozone
B B □
Wall-mounted version with IP66 protection
rating (144 x 144x 120 mm)
3 »"42ji'&>'
I
Panel-mounted version
(144x144x100 mm]
Process control device
Display
► Simultaneous measurement (numerical and bar graph) and
temperature values.
► Scrolling output values.
► Graphic icons for: status of digital outputs, washing cycle,
data recording, alarms.
► Possibility to display the measurement only in large format.
Data recording
► 4-bit internal flash memory (about 16,000 records).
► Recording interval: 1 to 99 min.
► Type: Circular (F.I.F.O.) or filling.
► Ability to view the logged data in table or graphic form, with
indication of the maximum, minimum and average values in
the selected periods.
PID control
► P - PI - PID functions activated on the analogue or digital
output.
► Proportional range: 0 to 500%.
► Integral time: 0:00 to 5:00 min.
► Derivative time: 0:00 to 5:00 min.
2 analogue outputs
► Output 1 programmable for measurement.
► Output 2 programmable for measurement / temperature /
PID control.
► The limits of the outputs are freely programmable within the
measuring range.
4 digital outputs
► ON/OFF set point: Programming the operating range
(hysteresis/direction) and start/stop time 000 to 999 seconds.
► PID control: Pulses, frequency or PWM (2 set points).
OChemitec
"