RAK: Universal thermostat0 pages
21.610/1
RAK: Universal thermostat
How energy efficiency is improved
Demand-led controlling, monitoring and limiting, without auxiliary energy.
Areas of application
For controlling and monitoring the temperature of liquids in baths, tanks, pipelines and ducts. Thanks to
modular design, can be used as controller, monitor, limiter or safety limiter.
Features
Temperature range: –10 to +230 °C
Classified as Cat. IV according to DGRL 97/23/EC
<45 s time constant in water
Thermostat with remote sensor
Clamp-on thermostat
Capillary-tube thermostat with and without protective tube
Double thermostat e.g. as TW and STB
T
Technical description
Two-part housing made of plastic, lower part black, upper part yellow, including inspection
window
0,8, 1 and 1,6 m capillary tube length
Also for flue gas pipes
As a temperature controller-monitor (TW); with LW 7 pocket, brass, 100 mm; as per DIN 3440
RAK 582.4/3773
5...30
4
800
68
200
RAK 582.4/3770
–10...50
4
1600
68
180
RAK 582.4/3728
15...95
4
800
68
200
RAK 582.4/3754
40...120
4
1600
68
200
RAK 582.4/3726
50...130
4
800
68
200
80...160
4
1600
68
200
RAK 582.4/3729 3) 5)
150...230
4
1000
68
280
RAK 582.4/3753 3) 5)
As a safety temperature limiter (STB), classified in PED 97/23/EC as per Cat. IV; with LW 7 pocket,
brass, 100 mm; as per DIN 3440; intrinsically safe; with mechanical lock.
RAK 13.5050S
130/120/110/100/95 1)
20
800
68
170
As a temperature limiter (TB); with mechanical lock;
with LW 7 pocket, brass, 100 mm; as per DIN 3440
RAK 584.4/3782
20...60
10
800
68
200
RAK 584.4/3783
50...130
10
800
68
220
As STB for exhaust pipes with sensor tube and pocket; as per DIN 3440; intrinsically safe; with lock
RAK 574.4/3715
120/100/80
20
800
91
230
RAK 574.4/3720
160/140/120
20
800
91
240
RAK 574.4/3797
200/180/160
20
800
91
250
Max. contact rating 2)
Terminal 1-2 TW, TB
Terminal 11-12 STB
Terminal 1-4 TW
Min. contact rating
Time constant in water
without pocket
with LW 7 pocket
Calibration point
TW, TB
STB
Influence of head temperature
depends on type
Weight
Transport and storage temp.
Permissible ambient temp. (housing)
as clamp-on sensor (water temp.)
1)
2)
3)
4)
5)
10 (2.6) A 250 V~
10 (6) A 250 V~
4 (0.6) A 250 V~
500 mA 40 V
< 15 s
< 45 s
23 2 °C (Tu 23)
37 2 °C (Tu 37)
Type of protection
Protection class
DIN register number
Not classified in the PED
Classified in the PED 97/23/EG
as per Cat. IV:
Test marking 4)
Wiring diagram
0,20...0,60 K/K
0,22 kg
–25...75 °C
0...70 °C (T70)
max. 130 °C
TW
STB
TB
T
Y02115
T
°C
Switching Capillary Sensor Max. temp.
difference
tube
cartridge of sensor
K
mm
mm
°C
Xs
Setting range
Xsd
Type
Y02103
3 2
1
B01571
IP 54 (EN 60529)
I (IEC 60730)
RAK 574.4, 584.4
and 582.4
RAK 13.50 . . S
ID: 0000006982
RAK 13.50 . .
A10391
A10396
A10394
M05633
MV 505803
Dimension drawing
Fitting instructions
Settings (via catches) are irreversible
If under inductive load, take RC circuit into account.
Pocket included; stainless-steel pockets should be used above 130 °C; see chapter 29, pocket LW 7 Niro
Certificates can be downloaded from www.tuv.com
Distance piece 100 mm for temperatures > 130 °C included
Sauter Components
7121610003 07
"