Selective Level Meter SLM35050 pages
Selective Level Meter
SLM3505
Field Portable Power Line Communications Analysis
Instrument Functions
Single and Dual Frequency
Selective Level Meter
Impedance Analyzer (LCR Measurements)
Frequency Response Analyzer
VSWR Meter
Signal Generator
Oscilloscope
Applications
Power Line Carrier Alignment &
Maintenance
Line Trap Alignment & Test
Line Tuner Alignment & Test
PLC Transmitter & Receiver Test & Set-up
Audio Tone Protective Relay Channel Test &
Set-up
FSK Telemetry Testing
The SLM3505 was designed to provide a single instrument solution for the Electric Utility System Protection Engineer and
Relay/Communications Technician responsible for the alignment and maintenance of Power Line Carrier, Audio Tone and FSK
Communications Systems. This multifunction instrument replaces all 4 existing Power Line Carrier Instruments in one for a fraction
of the cost, all in a compact lightweight package.
Featured Application Highlights
LINE TRAP TESTING
LINE TUNER TESTING
The SLM3505’s Impedance Analyzer provides an impedance
versus frequency plot directly on the display. A technician can
therefore view a curve representing the resonant frequency
and adjust a trap and tuning pack while viewing the changes
in a real time environment, without having to adjust the meter.
Since the SLM3505 is a true LCR Meter with the ability to
zero out cable impedance, test lead length and separation is
no longer a concern. Now the technician can attach long
leads to a mounted trap and perform testing while still on the
ground, by simply zeroing the capacitance in the leads.
The SLM3505 provides a single instrument solution for
adjusting a Tuner’s Series inductor and Impedance Matching
transformer for minimum reflected power. The 3505
achieves this either with a conventional directional coupler
technique or by an innovative impedance comparison
technique that achieves the same measurement results
without the need for any additional hardware. Using either
technique in VSWR mode, a single screen displays the
frequency under test, the forward power level, the reflected
power level and the % reflected power.