1. Overview
1.1 Introduction
DL200 is a data logger which can connect up to 247 Network
Temperature Controllers Model NC200. This unit can write all
commands and read all data to and from each Network
Temperature Controllers Model NC200 after equipping the unit
with a HMI or PC via RS-232 port. The unit provides a dry
contact which will be closed when one or more of the Network
Temperature Controllers Model NC200 are outside of high and
low limits or hardware failure occurs.
Power Input
4: 90 ~ 250 VAC,
~ 63 HZ
47 1. RS-232, Modbus protocol
9: Special order
Communication
1: Form A Relay,
2A/250VAC
Alarm Output
DL200-
0: No special option
Options
Standard ordering code = DL200-4110
1.2 Ordering Code
1.3 Front Panel
Figure 1 Front Panel Description
The dual-color LED on the front panel provides following
status:
Green: All the controllers in the network are within their
temperature limits and no failure exist.
Red: One or more of the controllers are outside of high
and low limits, or hardware failure exist.
Off: Power is not supplied.
Two green LEDs on the front panel will be flashing when
data are being received from HMI or transmitted to HMI
or PC via RS-232 port.
2. Installation
T
PWR(G)
CAT. II
90-264VAC
47-63HZ 10VA
RS-
L N
HMI
or
PC
90 ~ 250 VAC
FUSE
NC200 #1 NC200 #2
9-pin
RS-232 port
Female
9-pin D-SUB
AL(R)
COMM
IN
COMM
OUT
COMM
IN
COMM
OUT
Figure 2 System Wiring
In addition to two screw holder located at two corners of the
for wall mount installation, a DIN rail clamper provided on the
side of the housing for DIN rail mount installation.
3. Modbus Communication
3.1Modbus Functions Supported
Only function 03, 06 and 16 are available for this unit.
The message formats for each function are described as follows:
Query ( from master ) Response ( from slave )
Slave address (20)
Function code (3)
Starting address of register Hi
Starting address of register Lo
No. of words Hi (0)
No. of words Lo (1-127)
CRC16 Hi
CRC16 Lo
Byte count
Data 1 Hi
Data 1 Lo
Data 2 Hi
Data 2 Lo
CRC16 Hi
CRC16 Lo
Function 03: Read Holding Registers
5. Specification
UMDL200B 1
1.1 Introduction
1.2 Ordering Code
1.3 Front Panel
1. Overview
3. Modbus Communication
2. Installation
3.1 Modbus Functions Supported
3.2 Modbus Exception Responses
3.3 Modbus Parameter Table
3.4 RTU Communication Examples
4. Operation
4.1 ONLINE
4.2 CODE
4.3 Alarm Output
Dual-color LED
Green LEDs
R: Receive from master
T: Transmit to master