IsolatingRepeater_AK00_III_0 pages
Fibre Optics Fieldbus Isolating Repeater
Series 9186
> Easy installation and mainetance due to:
– Inherently safe optical interface
– Intrinsically safe bus connection via
RS-485 IS (PNO)
> High availability due to:
– Build-up of ring structures, redundant
Point-to-Point, line structures
– Integrated analysis of optical input
signal
– Error message if critical levels of
input signal reached
A3
A3
A3
> Transmission of Profibus DP, Modbus,
HART on RS-485, R. STAHL Servicebus
A3
> 9186/.5
– Installation in Zone 2 possible
A3
www.stahl.de
> 9186/12
– Installation in Zone 1 and Zone 2
possible
– Fieldbus interface for intrinsically
safe Profibus DP (PNO)
A3
Series 9186 A3
08579E00
A3
The Fibre Optic Isolating Repeater is used to build-up fibre optic network structures
in hazardous areas. It enables to transmit Profibus DP or Modbus signals over distances of up to 2 km or 1,2 miles. The optical interfaces are designed to be inherently
A3
safe (Ex op is). The protection scheme Ex op is allows to apply usual standardized
industry connectors. The Zone 1 / Div. 2 version of the Fibre Optic Isolating Repeater
offers an intrinsically safe RS-485 interface acc. to the standard RS-485 IS (PNO).
A3
Critical levels of the received optical signal are detected by the integrated diagnostic
function. The fault is indicated by LEDs on the front side of the device and in addition
by a line fault contact. The contact is used to trigger a remote fault indication in the
control room. The diagnostic function enables preventive maintenance and
improves the availability of the plant.
IECEx / ATEX
NEC 505
A3
NEC 506
NEC 500
Class I
Class I
0
1
2
20
21
22
0
1
2
Division
1
2
1
2
1
2
9186/12-11-11:
Ex i interface
x
x
x
x
x
x
x
x
x
9186/12-11-11:
Ex i interface
x
x
x
x
x
x
x
9186/.5-..-..:
Ex i interface
x
x
9186/12-11-11:
Installation in
9186/.5-..-..:
Installation in
x
x
x
x
x
x
x
x
22
A3
x
x
21
Class III
Zone
9186/.5-..-..:
Ex i interface
20
Class II
x
x
9186/12-11-11:
Installation in
x
x
x
x
x
9186/.5-..-..:
Installation in
x
x
A3
x
A3
WebCode 9186A
2014-06-05·AK00·III·en
A3
Isolators
A3/1
"