Digital Indicating Controller LT1100 pages
DIGITAL INDICATING CONTROLLER
LT110 SERIES
LT110 series, 1/32 DIN size, miniature digital indicating
controllers, feature all functions that are convenient in
various control applications.
The controllers are applicable to various equipment
including semiconductor manufacturing equipment,
electronic
parts
manufacturing
equipment,
food-processing machinery, packaging machinery,
injection machine.
FEATURES
Small size, lightweight, short space
Universal input consisted of 5 kinds of T/C input and 4
kinds of RTD input, and multi-input of 5 kinds of T/C input
Optimum PID values are automatically calculated for
accurate and stable control by PID auto-tuning.
Various functions including sensor correction, setpoint lock,
setpoint limit, control output OFF, and alarm action delay
timer are built-in.
The controllers conform to CE and the front panel is
dust-proof and water-proof conforming to IP-65.
MODEL
0000 LT1 1
Hysteresis: 0.1 to 100.0°C (2-position control only)
Anti-reset windup: Automatic
Control operation: Direct/reverse operation switching
Output:
On-off pulse type
Output signal ……… On-off pulse conductive signal
Contact rating ……. Resistive load 250VAC 3A
Inductive load 250VAC 1A
On-off pulse time … Approx. 1 to 120seconds variable
Current output type
Output signal ……… 4 to 20mADC
Load resistance .….. 500Ω or less
SSR drive pulse type
Output signal ……… On-off pulse voltage signal
At ON 12VDC ± (0 to +2V), Max 40mA
On-off pulse cycle … Approx. 1 to 120 seconds variable
Output limiter: 0 to 100% (–5 to 105% for current output type)
0A
Size
1: 48 x 24mm
Input signal
0: Universal input (with 1 event output)
1: Thermocouple multi- input
Control output
1: On-off pulse type
3: Current output type
5: SSR drive pulse type
Options (Available in universal input only)
ALARM SPECIFICATIONS
Alarm point: 1 point
Temperature alarm type:
Deviation high alarm, deviation low alarm
Absolute value deviation high alarm, absolute value deviation low alarm
Deviation high alarm with standby function
Deviation low alarm with standby function
Absolute value deviation high alarm with standby function
Absolute value deviation low alarm with standby function
Absolute value high alarm, absolute value low alarm
Absolute value high alarm with standby function
Absolute value low alarm with standby function
Loop break alarm:
Alarm activation when the control output is maximum or minimum and the
process value does not vary more than a set band in a set time.
Heater disconnection, sensor disconnection, control equipment failure
Alarm time setting range: 0 to 200 minutes
Alarm band: 0 to150°C or 0.0 to 150.0°C
Alarm deadband: 0.1 to 100°C
Alarm output: Open collector 24VDC 0.1A (maximum)
0: None
1: Setpoint change (DI) ...
With 2 SVs and 1 DI
2: Heater disconnection (CT)
… With current transformer
Available in on-off pulse type and SSR
drive pulse type only
Power supply
A: 100 to 240VAC (universal)
SPECIFICATIONS
INPUT SPECIFICATIONS
Input signal:
T/C … K, N, J, E, Platinel II
RTD … Pt100, JPt100
Measuring range: Refer to the measuring range.
Indication accuracy ratings:
T/C…±0.3% of input span ± 1 digit or ±2°C, whichever is larger
RTD…±0.2% of input span ± 1 digit
Measuring unit: °C or °F
Sampling time: Approx. 0.25 second
Burnout: Upscale
Allowable signal source resistance: T/C … 100Ω or less
RTD … 10Ω or less (per wire)
Measuring input shift (sensor correction): -100.0 to 100.0°C
DISPLAY FUNCTION
Display: 4-digit LED
Display contents: PV or SV switching, Parameter item
GENERAL SPECIFICATIONS
Power voltage: 100 to 240VAC, 50/60Hz (universal)
Working temperature: 0 to 50°C
Working humidity: 35 to 85%RH (no dew condensation)
Power consumption: Approx. 5VA
Case: Non-flammable resin
Color: Gray
Installation: Flush panel installation
Weight: Approx. 100g
CONTROL SPECIFICATIONS
Control cycle time: Approx. 0.25 second
Control system: PID (2-position control enabled)
Control setting accuracy ratings:
Same as indication accuracy rating
Auto-tuning: Standard (Manual setting of PID constants enabled)
PID constants: P … 0 to Maximum value of each range
I …. 0 to 3600 seconds
D … 1 to 3600 seconds
Pulse cycle: 1 to 120 seconds (Available in on-off pulse type and SSR pulse
type only)
1