FPA38, kW transmitter, symmetrical0 pages
C-mac
®
kW transmitter FPA38
Transmitter for kW, 3-phase symmetrical load
Connection to 3-phase net up to 3 x 500 VAC
Monitoring of total power consumption (Ö3 x U x I x cos j)
Built-in current transformer, ranges up to 60 AAC
Analogue output 0-20 mA / 4-20 mA
24 DC supply
Galvanic separation, input - output
Made in accordance with the
and EMC regulations
FPA38 is monitoring the power consumption on 3-phase
symmetrical load, primary motors.
The wanted metering range is selected by means of
DIP-switches, from 0-3,46 kW up to 0-41,6 kW at 3x400
VAC supply, proportional to 0-20/4-20 mA on the metering output. 0-10 V is also possible, see below.
The supply voltage, 24 VDC, and the 3 voltage phases are
connected to the relevant terminals. The current is monitored by putting the current phase L1 through the built-in
current transformer, see connection diagram.
Technical data:
Supply voltage:
Current consumption:
Operating temp.:
Metering rangeV:
Metering range I:
Metering range f:
Accuracy:
Analogue output:
Note:
Load, outputs:
Note:
Reaction time:
Weight:
Dimensions:
CE mrk:
24 VDC +/- 5%
max. 60 mA
-15 to +50°C
3x200 to 3x500 VAC
5, 10, 20, 25, 40, 60 A
10-150 Hz
Class 2
selectable 0-20 mA or 4-20 mA
For 0-10 V output,
select 0-20 mA, and then connect
pin 7 and 8 (GND og X1)
The metering output is not galvanic
separated from 24 VDC supply.
Current: max. 500 Ohm
Voltage: min. 100 kOhm
Output is short-circuit proof
approx. 200 msec.
200 g
90 x 35 x 57 mm
EN61326A, LVD EN61010
Selection of metering range
The wanted ranges are selected with the DIP-switches on the
side of the unit.
Select output signal, 0-20 mA or 4-20 mA with SW1.
SW2, 3 and 4, selection of monitoring current, see table.
SW1
SW2
SW3
SW4
Amp
kW
OFF = 4-20 mA
OFF
ON
OFF
OFF OFF
ON
OFF OFF OFF
5
10
20
3,46 6,92 13,8
ON = 0-20 mA
ON
OFF
ON
ON
OFF
ON
OFF
ON
ON
25
40
60
17,3 27,7 41,6
Note: The power ranges in the table are calculated and
calibrated with a supply voltage of 400 VAC.
Connection diagram.
L1
L2
L3
1 L1(U)
3 L2(V)
5 L3(W)
+24V 6
GND 7
X1 8
Iout 9
GND 10
Supply
FPA38
LOAD
Metering principle.
The FPA 38 is connected to the supply, 3-phase net and
load as shown above.
It can also be used together with frequency converters, as
it operates in the frequency range10-150 Hz.
For monitoring of 1-phase loads, connect L2 and L3 to N,
and L1 to the phase.
Since the unit is calibrated for 3-phase loads, the output
signal must be multiplied with 1.5 in order to get the correct value at 1-phase loads.
Comadan
Produktion a/s
6-11
"