FLEX6005A0 pages
FLEX6005A
RoHS
Input: single-phase: 115 – 230 Vac
Output: 5 Vdc 50°C
Efficiency up to 88%
Strong overload without switch-off
Flexible Power continuity : up to 35 W
DIN Rail Mountable
Extremely small size
3 Year warranty
Features
Input Data
Norms and certifications
Nominal Input Voltage (2 x Vac)
Input Voltage range (Vac)
Inrush Current (Vn and In Load) I2t
Frequency
Input Current (115 – 230 Vac)
Internal Fuse
External Fuse (recommended)
115 – 230 Vac
90 – 264
7 A 5 msec.
47 – 63 Hz 6%
0.5 – 0.25 A
T4A
6 A (MCB curve B)
The CE mark in According to EMC 2004/108/EC and Low
voltage directive 2006/95/EC.
Output Voltage (Vn) Factory Setting 3%
Adjustment range (Vadj)
Start up with Strong Load (capacitive load)
Turn-On delay after applying mains voltage
5 Vdc
4.75 – 5.25 Vdc
50.000F
2 sec. (max)
EMC Immunity
Continuous Current at 5 V up to 50°C (In)
Power Boost Current at 5 Vdc up to 50°C(In)
Current max. Overload 2Vdc (permanent)
Max current Short Circuit (Icc)
Hold-up Time ( min. Vac) 5Vdc 5A
Residual Ripple
Efficiency
Over temperature Protection
5 A (115-230)
7 A up to 3 min.
Imax=In50°Cx(1.3-1.4)
10 A
Typ. 20 msec
80 mVpp
88 %
Yes. Shut-down output
and automatic restart.
Yes, Continuous Mode
3
Yes, Continuous Mode
Yes (typ. 15 Vdc)
Yes
Output Data
Short-circuit protection
Dissipation power load max (W)
Over Load protection
Over Voltage Output protection
Parallel connection
Climatic Data
Ambient Temperature Storage
Humidity at 25 °C, no condensation
In compliance to UL508.
According to IEC/EN 60950 (VDE 0805) e EN 50178 (VDE
0160) for assembling device. The unit must be installed
according to IEC/EN 60950.Input / Output separation: SELV
EN60950-1 6 Edition, and PELV EN 60204-1. Double or
reinforced insulation.
EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5,
EN 61000-4-6, EN61000-6-2
EMC Emission:
EN61000-6-4, EN61000-3-2
Standards Conformity
EN 60204-1 Safety of Electrical Equipment Machines
Output derating Curve
Continuous Load
% 160
140
120
100
80
60
40
20
0
-10
0
10
20
30
40
50
60
70 °C
-25 up to +70 °C
(>50°derating 2.5% °C)
-40 up to +85 °C
95 % to 25 °C
Isolation Voltage (In / Out)
Isolation Voltage (In / PE)
Isolation Voltage (Out / PE)
Protection Class (EN/IEC 60529)
Reliability: MTBF IEC 61709
Pollution Degree Environment
Connection Terminal Blocks Screw Type
Protection class
Dimension (w-h-d)
Weight
Electrical Safety
3000 Vac
1605 Vac
500 Vac
IP 20
> 500.000 h
2
2,5 mm (24 – 14 AWG)
I with PE connected
50x120x50 mm
0.3 kg approx.
Ambient Temperature operation
General Data
All specifications are subject to change without notice
"