CBI1235A ALL In One0 pages
1Can be adjusted via PC software mode
All specifications are subject to change without notice
Input: Single-phase 115 – 230 Vac
Output Load: power supply 12 Vdc; 35 A
Output Battery: charging 12 Vdc; 35 A
Suited for the following battery types: Open Lead Acid, Sealed Lead Acid, lead Gel and Ni-Cd
Automatic diagnostic of battery status. Charging curve IUoUO, constant voltage and constant current Battery Life Test function (Battery Care)
Switching technology, output voltage 10-14.4 Vdc Three charging levels: Boost, Trickle and Recovery
Protected against short circuit and inverted polarity
Signal output (contact free) for discharged or damaged battery
Signal output (contact free) for mains or Back-UP
Protection degree IP20 - DIN rail; Space saving
Technical features
Thanks to the All In One units (DC-UPS), it will be possible to optimize power management. The available power is automatically allocated between load and battery, supplying power to the load is the first priority of the unit thus it is not necessary to double the power, because also the power going to the battery will go to the load if the load so requires. The maximum available current on the load output is 2 times the value of the device rated current In. We call “Battery Care” the concept base on algorithms that implement rapid and automatic charging, battery charge optimization during time, flat batteries recovery and real time diagnostic during installation and operation. The Real Time Auto-diagnostic system, monitoring battery faults such as, battery Sulfated, elements in short circuit, accidental reverse polarity connection, disconnection of the battery, they can easily be detected and removed by help of Blink Code of Diagnosis Led; during the installation and after sell. The continuous monitoring of battery efficiency, reduces battery damage risk and allows a safe operation in permanent connection. Each device is suited for all battery types, by means of jumpers it is possible setting predefined curves for Open Lead Acid, Sealed Lead Acid, Gel, Ni-Cd(option). They are programmed for two charging levels, boost and charge, but they can be changed to single charging level by the user. A rugged casing with bracket for DIN rail mounting provide IP20 protection degree. They are extremely compact and cost-effective.
Norms and Certifications
In Conformity to: IEC/EN 60335-2-29 Battery chargers; EN60950 / UL1950 Electrical safety; EN54-4 Fire Detection and fire alarm systems; 89/336/EEC EMC Directive; 2006/95/EC (Low Voltage); DIN41773 (Charging cycle); Emission : IEC 61000-6-4; Immunity: IEC 61000-6-2. CE.
Climatic Data
Ambient temperature (operation)
-25 ÷ +70°C
De Rating Ta > 50°C
- 2.5%(In) / °C
Ambient temperature Storage
-40 ÷ +85°C
Humidity at 25 °C no condensation
95% to 25°C
Cooling
Auto convention
General Data
Insulation voltage (IN/OUT)
3000 Vac
Insulation voltage (input / ground)
1605 Vac
Insulation voltage (Output / ground)
500 Vac
Protection Class (EN/IEC 60529)
IP20
Reliability: MTBF IEC 61709
> 300.000 h
Pollution Degree Environment
2
Connection Terminal Blocks screw Type
4 mm (30-10 AWG)
Protection class (PE Connected)
I, with PE
Dimensions (w-h-d)
150x115x135 mm
Weight
1.55 kg approx.
Input Data
Nominal Input Voltage
115 – 230 Vac
Voltage range
90 ÷ 264 Vac
Inrush Current (Vn – In nom. Load) I2t
„T 35 A „T 5 msec.
Frequency
47 ÷ 63 Hz
Input Current (115 – 230 Vac)
8 – 4.2 A
Internal fuse (not replaceable)
10 A
External Fuse (recommended) MCB curve B
16 A
Output Data (internal power supply)
Output Voltage (Vn) / Nominal Current (In)
12 Vdc / 35A
Output Current In
35 A
Efficiency (at 50% of rated current)
„d 91 %
Turn-On delay after applying mains voltage
1 sec. (max)
Start up with Strong Load (capacitive load)
Yes, Unlimited
Dissipation power load max (W)
28
Short-circuit protection)
Yes
Over Load protection
Yes
Over Voltage Output protection
Yes (typ. 35 Vdc)
Over Eating Thermal protection
Yes
Battery Output
Boost charge (25 °C) (at In)
14.4 Vdc
Max. time Bust Charge
15 h
Min. time Bust Charge
1 min.
Trickle charge (25 °C) (at In)
13.75 Vdc
Jumper Configuration battery type
(V cell) Ni-Cd (optional)
2.23;2,25;2,27;2,3; 1,41–1,5 (20 elem.)
Recovery Charge
2 – 9 Vdc
Charging current max Ibatt
35 A „b 5%
Charging current limiting Iadj
20 ÷ 100 % / Ibat
Reverse battery protection
Yes
Sulfated battery check
Yes by Jumper
Detection of element in short circuit
Yes
Quiescent Current
„T 5 mA
Charging Curve automatic: IUoUo
3 stage
Remote Input Control (AMP type connector)
Boost /Trickle
Load Output
Output voltage (at In)
10 - 14.4 Vdc
Nominal current Iload
1.1 x In A „b 5%
Continuous current (without battery) Iload= In
35 A
Continuous current ( With battery) Iload= In+ Ibatt
70 A
Max. current Output Load (Main) Iload (4 sec.)
105 A max.
Max. current Output Load (Back Up)Iload (4 sec.)
70 A max.
Push Bottom or
Remote Input Control (AMP type connector)
Start From Battery Without Main
Time Buffering; min (switch output off without main input) 1
0.5;1;3;5;10;15; 20; 30; 45;60;‡
Protections against total discharge 1
9 – 10 Vdc batt
Threshold alarm Battery almost flat 1
10 – 11 Vdc batt
Signal Output (free switch contacts)
Main or Backup Power
Yes
Low Battery
Yes
Fault Battery
Yes
Type of Signal Output Contact
Max. Current can be switched (EN60947.4.1):
Max. DC1: 30 Vdc 1 A; AC1: 60 Vac 1A
Min.1mA at 5 Vdc
Resistive load
Min permissive load
Signal Input / Output (RJ45)
Temp. Comp. Battery (with external probe)
Yes
Remote monitoring display
Yes
Can Bus
Optional