DFS 4 016-4/0,01-A FT0 pages

نسخه متنی
"

Doepke
The experts in residual current protection technology

DATA SHEET

Internetlink

DFS 4 016-4/0,01-A FT
pulsating AC/DC-sensitive type A, with remote-tripping function
Article No. 09112921

Symbolic image

1AT
Function
Residual current circuit-breakers (RCCBs) are components for implementing protective measure "Automatic switch-o of power supply"
as per VDE 0100 part 410 or corresponding international installation regulations. Series DFS 4 devices are compact two or four-pole
residual current circuit-breakers. In the standard design, they only take up four module width units of space. While DFS 4 devices are
designed for AC and pulsating DC residual currents for three-phase networks but can also be used in single-phase networks, there are also
special variants in the AC/DC sensitive designs (type B, type B+) for single or three-phase operation. In spite of the compact dimensions,
a number of dierent tripping currents and characteristics are available at rated currents, depending on the design, up to 125 A. Usually
the neutral conductor connection is located on the left side, but can be on the right if desired. Furthermore, all devices are available in the
"HD" design, which is especially suitable for use in extreme environments (tunnels, swimming pools, etc.) They also have large two-tier
terminals for large conductor cross-sections, a practical multifunctional switch toggle and can be provided with pre-prepared labels using
free-of-charge software. Switches with residual current characteristic A are independent of the mains voltage and allow the detection of
sinusoidal AC currents and pulsating DC residual currents. With the FT design the connections of the internal test key are wired to two
terminals in order to be able to activate the test device externally. An auxiliary contact also reports the switch-o of the safety switch.
Features
integrated auxiliary switch function, contact data same as for DHi, The technical properties of the basic switch are not changed by the
FT option., tripping not dependent on mains and auxiliary voltage, sensitive to AC residual currents and pulsating DC residual currents
(type A), compact design for all rated currents, high short-circuit resistance, double-sided two-tier terminals for large conductor crosssection and busbar, switch position indicator, viewing window for labels, multifunction switch toggle with three positions: "on", "o" and
"tripped", , neutral conductor in standard design left, optionally available: N right for any four-pole device at no extra cost
Mounting
quick fastening to mounting rail, any installation position, supply from any direction
Applications
Power supplies to residential and purpose-built buildings as well as industrial facilities with TN-S, TT and TN-C-S networks. In IT networks,
the residual current circuit-breakers of this series can be set to switch o in the event of a second fault, RCCBs from the "FT" series are
especially suitable for the remote switch-o of systems and parts of systems and for being tripped by hazard alarms, amongst other
devices, Not permitted for use in TN-C networks; not permitted for protecting systems in which electronic equipment may cause smooth
DC residual currents or residual currents with frequencies not equal to 50 Hz. Comprehensive protection is not provided in this case. For
these applications we recommend our AC/DC sensitive residual current circuit-breakers (type B or B+).
Notes
Do not use as emergency stop circuit!, The contacts of the external command device must be designed for a rated residual current ≥ 0.5 A
and for the rated voltage of the residual current circuit-breaker.
Accessories
KA-DFS2, WES, Labelling software for DLS 6, DFS 2/4
Technical Data
Series
Number of poles
Residual current type
Rated current (AC)
Rated residual current I∆n
Short-time delayed

2015_03_13

DFS 4 016-4/0,01-A FT
DFS 4
4
A
16 A
0.01 A
false

doepke_09112921_dbl_en.pdf

1/4

"

IRAN INDUSTRY EXPO

The largest online Industrial exhibition in Iran

 عضویت ورود   ENGLISH


اگر مجموعه شما جزو صنایع مادر و معظم در فیلد پالایشگاه ، پتروشیمی ، حفاری ، نیروگاه ، معادن و فلزات ، خودروسازی ، تولید مواد غذایی و.... می باشد لطفا درخواست خود را بر روی سربرگ به فاکس 88206264 و یا ایمیل enquiry@iranindustryexpo.com بنام شرکت مهندسی و بازرگانی مشگاد ارسال فرمایید.
اگر مجموعه شما جزو بنگاه های متوسط و کوچک در فیلد تولید ، بازرگانی ، مشاوره ، پیمانکاری ، دانشگاه ، پژوهشگاه ، توزیع ، فروشگاهی وکارگاهی می باشد ، پس از عضویت و با پرداخت هزینه ( به ازای هر درخواست معادل 50 یورو ) از خدمات زیر برخوردار خواهید شد :
  • پاسخ به پرسش های فنی و دریافت مشاوره از سازنده ، دریافت کاتالوگ و اطلاعات تکمیلی
  • دريافت پرفورما از شرکت سازنده
  • اطلاع از زمان تحويل و قيمت خالص كالا
  • اطلاع از هزينه هاي حمل و ترخيص و کارمزد تا تحويل كالا به انبار شما در هر نقطه از كشور
  • دریافت پیش فاکتوررسمی ( ارزی و یا ریالی ) به روش کارمزدی
*صدور پیش فاکتور رسمی فقط به نام شرکتهای ثبت شده که دارای کد بازرگانی معتبر باشند انجام پذیر است. در صورتیکه در حین مکاتبه با شرکت سازنده مشخص شود که دارای نماینده انحصاری و یا شعبه در ایران بوده و یا به به هر دلیل شرکت سازنده از فروش کالا به بازار ایران استنکاف نماید ارایه این سرویس متوقف و وجه دریافتی به حساب کاربر عودت می شود

ادامه