Model C1477-2 Omni8u 20-60Vdc0 pages
Omni-8µ
Model C1477 8 Point Micro Annunciator 48x96mm DIN Housing.
DATASHEET
Features
•
•
•
•
•
•
•
•
•
•
The smallest Annunciator yet – 48x96mm
8 Potential Free Contact Inputs
Normally Open/Closed Sense Selectable
22 Standard Sequences
Backlit LED Technology
User printed legends user inkjet/laser
Four function Group Alarm output contact
12Vdc, 20-60Vdc, 85-264Vac/dc powered
Motor Alarm Sequence options
Fully “Dip” Switch Configurable
The Omni-8 micro is the smallest annunciator yet from
Omniflex, designed for use in space restricted areas and
low input counts. Omni-8 micro is a fully self-contained
panel mounted annunciator with integral Test, Silence,
Acknowledge, Reset Pushbuttons and audible device.
The 8 inputs accept potential free inputs and are
individually switch configurable for normally open or
normally closed input operation. Inputs are wired to plugin terminals at the rear of the annunciator. The alarm
sequence for the eight inputs is also configured by DIP
Alarm Sequence and Input Sense Selection
switch with a choice of 22 standard sequences. A group
alarm or horn output is available on a change over
contact at the terminals. The relay contact can be set to
one of four functions: Follows input, Follows alarm,
Multiple reflash or Horn.
Input 8 may be designated as an Inhibit input which
enable the inputs on the annunciator to be disabled
during maintenance and startup periods etc. The 8th
window then acts as an inhibit indicator.
Electrical Connections
-
SW1
Alarm Sequence
We
S
mnWc
aq12S
rS Sie
A53 e
le 5
uS
342e
2c 1n
1e 4stl
8
7o
6n
1 2 3 4 5 6 7 8
ON
SW2
Sense Selection
+
~
PSU
Earth
1 2 3 4 5 6 7 8
ON
Not Used
Sequence Options
N.C.
Seq. No.
Sequence Description
Com
1
2
3
4
5
6
7
8
9
10
11
12
13
18
21
23
24
25
26
27
28
30
31
LAMP FOLLOWS INPUT
MOMENTARY (FLEETING) ALARM, MANUAL RESET
ALARM ONLY (NON-LATCHING INPUTS) AUTO RESET
MOMENTARY ALARM, MANUAL RESET WITH ALARM RINGBACK
FIRST OUT, MULTIPLE GROUPS, MANUAL RESET
FIRST OUT, MANUAL RESET, AUTO RESET ON SUBSEQUENT ALARMS
FIRST OUT, SINGLE GROUP, MANUAL RESET, FIRST OUT CONTINUOUS FLASH
FIRST OUT, MANUAL RESET, SUBSEQUENT ALARMS WITHOUT HORN
MOMENTARY ALARM, MANUAL RESET, AUTO SILENCE AFTER TIME DELAY.
MOMENTARY ALARM, MANUAL RESET, REALARM AFTER TIME IF STILL ABNORMAL.
MOMENTARY ALARM, MANUAL RESET, CONSTANT FLASH (FOR MOTOR ALARMS).
MOMENTARY ALARM, AUTO RESET, TIME DELAY ON RETURN TO NORMAL.
PULSE MONITORING ALARM; MANUAL RESET
MOMENTARY ALARM, AUTO RESET
FIRST OUT, MULTIPLE GROUPS, AUTO RESET
FIRST OUT, SINGLE GROUP, AUTO RESET, FIRST OUT CONTINUOUS FLASH
FIRST OUT, AUTO RESET, SUBSEQUENT ALARMS WITHOUT HORN
MOMENTARY ALARM, AUTO RESET, AUTO SILENCE AFTER TIME DELAY.
MOMENTARY ALARM, AUTO RESET, REALARM AFTER TIME IF STILL ABNORMAL.
MOMENTARY ALARM, AUTO RESET, CONSTANT FLASH (FOR MOTOR ALARMS)
PULSE MONITORING ALARM, AUTO RESET
INPUTS 1-4 SEQUENCE 1; INPUTS 5-8 SEQUENCE 27 (FOR MOTOR ALARMS)
< RESERVED >
Horn/Group
Alarm Relay
N.O.
V excite
I/P 8
I/P 7
I/P 6
I/P 5
I/P 4
I/P 3
I/P 2
I/P 1
Copyright Omniflex ♦ Subject to change without notice
Datasheet DSC1477R09 sheet 1 of 2
http://www.omniflex.com
®
"