FLEX17012A0 pages
FLEX17012A
RoHS
Input Data
Nominal Input Voltage (2 x Vac)
Manual select Input from 115 to 230
Input Voltage range (Vac)
Inrush Current (Vn and In Load) I2t
Frequency
Input Current (115 – 230 Vac)
Internal Fuse
External Fuse (recommended)
Output Data
Output Voltage (Vn) Factory Setting 3%
Adjustment range (Vadj)
Start up with Strong Load (capacitive load)
Turn-On delay after applying mains voltage
Rated Current at 24 V 40°C (In)
Rated Current at 24 V 50°C (In)
Rated Current at 24 V 60°C (In)
Power Boost Current at 24 Vdc 60°C(In)
Current max. Overload 4Vdc (permanent)
Current Short Circuit Icc
Max 2 sec.: Hiccup mode
Permanent : Continuous Mode
Hold-up Time ( min. Vac) 24Vdc 5A
Residual Ripple
Efficiency
Over temperature Protection
Short-circuit protection
Dissipation power load max (W)
Over Load protection
Over Voltage Output protection
Parallel connection
Power Good Contact rating (EN60947.4.1):
Max. DC1: 30 Vdc 1 A; AC1: 60 Vac 1A
Min.1mA at 5 Vdc
Climatic Data
115 – 230 Vac
90 – 135
(115)
180 – 264 (230)
11 A 5 msec.
47 – 63 Hz 6%
2.8 – 1.3 A
T4A
10 A (MCB curve B)
12 Vdc
10 – 14 Vdc
50.000F
1 sec. (max)
14 A (permanent )
12 A (permanent )
10 A (permanent )
In (60°C) x 1.5 3 min.
Imax=In60°Cx(1.8 - 2.2)
Input: single-phase: 115 – 230 Vac
Output: 12 Vdc 60°C
Flexible Power continuity :from 120 to 180 W
Efficiency up to 91%
Strong overload without switch-off, up to 50%
“Power Good” Relay
Tree mode of output protections:
1) Hiccup mode
2) Continuous Out Mode
3) Manual Reset
DIN Rail Mountable
Extremely small size
3 Year warranty
Norms and certifications
The CE mark in According to EMC 2004/108/EC and Low
voltage directive 2006/95/EC.
Electrical Safety
In compliance to UL508.
According to IEC/EN 60950 (VDE 0805) e EN 50178 (VDE
0160) for assembling device. The unit must be installed
according to IEC/EN 60950.Input / Output separation: SELV
EN60950-1 and PELV EN 60204-1. Double or reinforced
insulation.
EMC Immunity
EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5,
EN 61000-4-6, EN61000-6-2
EMC Emission:
EN61000-6-4, EN61000-3-2
Standards Conformity
EN 60204-1 Safety of Electrical Equipment Machines
Output derating Curve
Continuous Load
20 A
Typ. 20 msec
80 mVpp
91 %
Yes. Shut-down output
and automatic restart.
1° Hiccup Mode
2° Continuous mode
3° Restart After Main
17
Yes
Yes (typ. 35 Vdc)
Yes
% 160
140
120
100
80
60
40
20
0
-10
0
10
20
30
40
50
60
70 °C
Resistive load
Min permissive load
Ambient Temperature Storage
Humidity at 25 °C, no condensation
-25 up to +70 °C
(>60°derating 2.5% °C)
-40 up to +85 °C
95 % to 25 °C
Isolation Voltage (In / Out)
Isolation Voltage (In / PE)
Isolation Voltage (Out / PE)
Protection Class (EN/IEC 60529)
Reliability: MTBF IEC 61709
Pollution Degree Environment
Connection Terminal Blocks Screw Type
Protection class
Dimension (w-h-d)
Weight
3000 Vac
1605 Vac
500 Vac
IP 20
> 500.000 h
2
2,5 mm (24 – 14 AWG)
I with PE connected
55x110x105 mm
0.60 kg approx.
Ambient Temperature operation
General Data
All specifications are subject to change without notice
"