DLS 6i B01,6-1 for use in industrial installations, B characteristic, 10 kA0 pages
Doepke
The experts in residual current protection technology
DATA SHEET
DLS 6i B01,6-1
for use in industrial installations, B characteristic, 10 kA
Article No. 09916012
Internetlink
Symbolic image
1TV
Function
An important stipulation of DIN VDE 0100 is to protect cables, lines and installation devices from overload and short-circuits. This
requirement can be met using miniature circuit-breakers (MCBs). In industrial installations and also in commercial buildings, they often
take on additional protection of equipment and devices where there are usually higher requirements than when used in residential
buildings. Miniature circuit-breakers utilise both the magnetic and heat eect of the electrical current. If the current jumps to a value that
is too high when a short-circuit occurs, the MCB interrupts the circuit using the magnetic eld of an energised coil. The heat that develops
when there is continuous overload causes the bimetal to warp, which trips the breaker. The miniature circuit-breaker series DLS 6 has a
wide selection of dierent types for a number of application areas. In addition to switches for residential and purpose-built buildings, it
also contains switches for industrial applications. The compact design provides lots of space for the wiring and the large clamping area,
as well as the option of using conventional wiring rails for easy processing. The series also has a large, folding label window and a clearly
labelled display for the operating status. A number of additional devices, such as undervoltage or operating current trips and auxiliary
and fault indicator switches, make universal use of the miniature circuit-breakers possible. The DLS 6i design is especially suitable for use
in industrial facilities, for example, due to its high rated switching capacity of 10 kA. The large selection of rated currents and tripping
characteristics also allow the use of the miniature circuit-breaker in many applications. Miniature circuit-breakers with characteristic B
ensure standard protection for lighting and socket circuits. As their short-circuit trip is three to ve times the rated current, they should
not be used to fuse-protect load circuits with high switch-on currents. They replace the former L or H characteristic.
Features
high rated switching capacity for use in industrial systems, screw terminals with strain-relief clamps with wide terminal crosssection range for rail and line wiring on both connection sides, designs with 1 to 4 protected poles, also available with unprotected
neutral conductor pole (1+N, 3+N), special quick fastening for removal of multiple miniature circuit-breakers from the bottom or top
interconnection, large, folding label window for a secure hold and protection of the label, use of conventional wiring rails, ON/OFF switch
position indicator on the switch toggle, accessories retro-ttable on the right, labelling software free of charge
Mounting
quick fastening to mounting rail, any installation position
Applications
suitable for use in power supplies for industrial facilities and purpose-built buildings or buildings for commercial use
Accessories
Labelling software for DLS 6, DFS 2/4, DHi 3, DHi 4, DHi 5, DHi 6, DHi 8, DHi-S10, DHi-S11, DASA 24, DASA 230, DUSA 230, Label sheet
DLS 6
Technical Data
Series
Number of poles
Tripping characteristic
Adjustment range of overload tripping
Adjustment range of short-circuit tripping
Tripping factor over frequency band
Test current factor tripping electromagnetic
Test current multiplier, trip, thermal
Test current factor retaining electromagnetic
Test current factor retaining thermal
2014_12_09
DLS 6i B01,6-1
DLS 6i
1
B
1.13 ... 1.45
3 ... 5
1.5 at DC; 1.1 at 100 Hz; 1.2 at 200 Hz; 1.3 at 300 Hz; 1.4 at 400 Hz
5
1.45
3
1.13
doepke_09916012_dbl_en.pdf
1/4
"