MA5010 pages
MA501
Digital Ammeter
Features:
• Liquid Crystal Display
• Single row, 4 digit
• Analog style bargraph indication
• True RMS measurement
• CT primary programable uptoSOOOA
• For 1 phase 2 wire electrical connection
• IP protection (Front Plate): IP65
Size: 48mm x 48mm (1/16 DIN)
Certifications: C€ c©us
LISTED
Technical Specifications
Display
Display
Digit
Digit Height
Display Range
Bargraph
Single row, Liquid Crystal Display
4
0.56" (14.2mm)
0-6200A
Analog style bargraph indication
Input Specifications
Electrical Connection
Input Type
Input Current Range
Continuous Max. Input Rating
Overrange Indication
Frequency
Resolution
Accuracy
Burden
Sampling Rate
Dielectric withstand Voltage
Rated Impulse withstand Voltage
1 0-2 wire
AC
50mA - 5A
6.2A
"Or" for input > 6.2A
50/60HZ
0.001, 0.01,0.1,1 A
(Depending upon CT Primary Setting)
±0.5% of CT Primary Setting
0.5 VA at 5 A
3 samples / second
2kV AC between auxiliary supply &
measuring input
2kV(1.2/50pS)
Supply Specifications
Auxiliary Supply
Power Consumption
240V AC ±20%, (50/60HZ)
110V AC ±20%, (50/60Hz)
12VAmax
Resettable Parameters
CT. Primary Settings
CT. Secondary Settings
5,10,15, 20,25, 30, 40,50, 60, 75,
80,100,125,150,175, 200, 250,300,
400,500,600, 630, 750, 800,1000,
1200,1500,1600, 2000, 2250,2500,
3000, 3200,4000,5000.
5A Fixed
Environmental Specifications
Temperature
Humidity (non-condensing)
Operating: -10 to +55°C (14 to 131°F)
Storage: -20 to +75°C (-4 to 167°F)
Upto 85% RH_
Mechanical Specifications
Mounting
Weight
Protection Level
Panel mount
113gms
IP65 for faceplate
Dimensions
52mm
46.5mm
3 ■*
Front bezel
Terminal Connections
3.5mm
68.5mm
i
Side view
Panel cutout
5tt,„ Cable Size (AWG): 20 to 14; Tightening Torque (Lb-inch): 6.018 to 6.992
s Size (mm1): 0.5 to 2.5; Tightening Torque (N-m): 0.68 to 0.79
Ordering Information
CT Type | Supply Voltage | Certification | ||
110V AC | 240V AC | C€ | LISTED | |
MA501 | ■ | |||
MA501-CU | ■ | ■ | ■ | |
MA501-110V | ■ | |||
MA501-110V-CU | ■ | ■ |
Note: CT Type-There is an internal CT with CT setting (5-5000A).
For current input >5A, external CT is required.
www.selec.com
"